1.
The IBC is a construction document. The IFC and NFPA 1 are:
2.
NFPA documents are:
3.
The I in IFC stands for
4.
Water flow testing of the water supply system in a community is usually done to determine the amount and _________ of the available water.
5.
A green color-coded fire hydrant, based upon NFPA recommendations, would be able to supply _________ gallons per minute.
6.
The smallest size pipes in a public water main system are typically referred to as
7.
A fire detection system that transmits an alarm signal to an off-site commercial alarm service has notified a ________ station.
8.
NFPA 10, which covers _________, was adopted by reference into the Wisconsin Administrative code.
9.
Dry and wet chemical systems are most likely to be found protecting ________.
10.
Building standpipe hose is commonly found stored on ________
11.
Fire inspectors should typically insure that stock is not stacked any closer to sprinkler heads than ________ inches.
12.
Sectional water control valves for sprinkler systems that are often found on the outside of a building are called __________
A. 
Outside stem and yoke valves
B. 
13.
A sprinkler system that is charged with air pressure above its water control valve is referred to as a ________ pipe system.
14.
The inspector needs to evaluate the fire department's emergency ______ to get its vehicles up to the structure.
15.
Fire drills are _______ for all commercial structures within Wisconsin.
16.
Emergency planning for a structure is the direct responsibility of the__________
17.
Exit doors, with some exceptions, shall open_____________
18.
A standard exit door width shall not be less than _________
19.
The portion of the means of egress that leads from the inside of a structure to the exit is called the exit __________.
20.
The permitted occupancy in an elementary classroom which is 25-feet by 20-feet would be ________.
21.
The square footage of a building, which is 55 feet wide, 150 feet in length, and 12 feet in height is _____ square feet.
22.
The fire flow for a structure is 2,500 GPM. The required fire flow for this structure if it were 30% involved would be ________ gpm.
23.
An example of a FIRE REACTION activity would be to conduct ________.
24.
An example of an activity to prevent the SPREAD OF FIRE would be the use of a _____
25.
An example of PREVENTING FIRES would include using _______.