Fire inspector I quiz questions - chapter 7
The means of egress contains smoke
Active fire-protection systems are in use
The total occupant load has been exceeded.
Monitors the condition of existing means of egress
Ensures the structure matches the surrounding buildings
Documents that the structure has adequate hazard insurance
Exit signs
Panic hardware
Automatic sprinkler system
Exit access
Exit
Exit waiting area
Exit discharge
Exit waiting area
Public way or an area of refuse
5 feet
10 feet
15 feet
Horizontal exit
Unenclosed ramp or stairs
Doors at ground level that lead directly to the outside of the building
Are of refuse
Unenclosed ramp or stairs
Doors at ground level that lead directly to the outside of the building
The exit and exit access must be at least 50% clear of obstructions
Only movable furnishings or decorations are allowed in the exit and exit access.
No furnishings or decorations may be allowed to obstruct or conceal an exit or exit access
Vertical exits
Horizontal exits
Exit passageways
Vertical exits
Exit passageways
Smokeproof enclosures
Vertical exits
Horizontal exits
Exit passageways
Warn occupants of a fire
Alert emergency personnel of the exact location of the fire
Separate occupants from fire, smoke, and other hazardous elements during escape
18 inches
24 inches
36 inches
If 30 or more people are in a room or occupancy
If 40 or more people are in a room or occupancy
If 50 or more people are in a room or occupancy
Open and close by remove control to allow easy access
Provide energy savings during times the building is in use
Close automatically to provide a smoke or fire barrier in a fire-barrier wall
Whether the building has easily accessible fire extinguishers
Whether or not the building has an automatic sprinkler system
What type of hazard insurance is carried by the building owner
Must have the same rating as the walls
Must have a higher rating than the walls
Can have a lower rating than the walls
Walls
Floors
Doors
Handrails are required on both sides of the stairs
Stairways must be at least 60 inches wide.
Each flight of stairs between landings must be no longer than 18 feet
Equal Access Law in 2000
Americans with Disabilities Act in 1990
United States standard building codes
They cannot be used as a means of egress in any structure
They may be used as part of a mean of egress in new construction
They may NOT be used as part of a means of egress in new construction
30
50
60
Each model code organization
Each type of occupancy classification
The number of occupants and the time of day
100 feet
150 feet
200 feet
Wait!
Here's an interesting quiz for you.