1.
Runouts from horizontal mains or branches shall be taken off ________ the centerline of the pipeline.
A. 
B. 
C. 
D. 
2.
While brazing medical-gas copper joints, a purge gas shall flow continuously to prevent the formation of copper oxide on the inside surface of the joint. What shall be used as a purge gas?
A. 
B. 
C. 
Oil-free, dry Nitrogen NF
D. 
3.
Which of the following filler metals shall be used to braze copper-to-copper joints in medical gas/vacuum distribution piping?
A. 
B. 
C. 
D. 
4.
Tubing for positive pressure medical gas systems delivered from the manufacturer shall be__________________.
A. 
B. 
C. 
Identified as “oxy” or “med”
D. 
5.
In positive pressure systems, area alarm sensors for vital life support and critical care areas shall be located on which side of the zone valve box assemblies?
A. 
B. 
C. 
D. 
6.
The master alarm system shall activate when the pressure in the main supply lines increase or decrease by __________ percent.
A. 
B. 
C. 
D. 
7.
All medical gas alarm systems shall have a ____________ audible indication for each condition monitored.
A. 
B. 
C. 
D. 
8.
The master alarm system shall consist of two or more alarm panels, a centralized computer system shall not be permitted to be used as a substitute for one of the required master alarm panels.
9.
Since dew point and carbon monoxide monitors are located upstream of the source valve, demand check fittings are not required.
10.
Where shall pressure indicators be provided for medical gas systems?
A. 
B. 
C. 
Outlet/inlet side of zone valve
D. 
11.
The scale range of positive pressure analog indicators shall have the normal reading fall within the_________ percentage of the gage scale.
A. 
B. 
C. 
D. 
12.
Station inlets for WAGD service shall be legibly marked to identify them and shall be of a type appropriate for the flow and vacuum level required by the facility’s gas anesthetic machines.
13.
The factory installed tubing on station outlets/inlets shall extend no further than ______ from the body of the terminal.
A. 
B. 
C. 
D. 
14.
Each station outlet/inlet for medical gas or vacuum shall be ____________.
A. 
B. 
C. 
D. 
15.
What is the name given to the shutoff valve installed on all lateral branch piping from a main or riser?
A. 
B. 
C. 
D. 
16.
A shutoff valve shall be placed at the immediate connection of each source system to the distribution piping system. What is the name given to the valve?
A. 
B. 
C. 
D. 
17.
All valves except zone valve box assemblies shall be ________________.
A. 
B. 
C. 
D. 
18.
Where instrument air systems are provided with standby headers, in the event of a compressor failure, the standby header shall automatically serve the system.
19.
What is the minimum number of compressors required in an instrument air system that employs a standby header?
A. 
B. 
C. 
D. 
20.
Instrument air systems shall be permitted to interconnect with medical air systems that have at least two or more compressors.
21.
The quality of the instrument air shall be _________________.
A. 
B. 
C. 
Free of hydrocarbon vapors
D. 
22.
A Level 1 dedicated WAGD source shall consist of _____ or more producers, each shall be sufficient to serve the peak calculated demand.
A. 
B. 
C. 
D. 
23.
Vacuum receivers shall be capable of withstanding a gage vacuum of ________ inches of mercury.
A. 
B. 
C. 
D. 
24.
Level 1 medical-surgical vacuum sources shall consist of an automatic means to prevent_____________ through any off-cycle vacuum pump.
A. 
B. 
C. 
D. 
25.
Carbon monoxide shall activate the required alarms when the CO level exceeds ________.
A. 
B. 
C. 
D.