Medgas100number2

Reviewed by Editorial Team
The ProProfs editorial team is comprised of experienced subject matter experts. They've collectively created over 10,000 quizzes and lessons, serving over 100 million users. Our team includes in-house content moderators and subject matter experts, as well as a global network of rigorously trained contributors. All adhere to our comprehensive editorial guidelines, ensuring the delivery of high-quality content.
Learn about Our Editorial Process
| By Pbarton
P
Pbarton
Community Contributor
Quizzes Created: 4 | Total Attempts: 22,957
| Attempts: 1,797 | Questions: 100
Please wait...
Question 1 / 100
0 %
0/100
Score 0/100
1. Locations for central supply systems and the storage of medical gases shall be secured with lockable doors or gates.

Explanation

The correct answer is true because it is important to secure the locations for central supply systems and the storage of medical gases with lockable doors or gates. This helps to prevent unauthorized access and ensures the safety and security of the medical gases, which are crucial for patient care. By having lockable doors or gates, healthcare facilities can control access to these areas and reduce the risk of theft, tampering, or misuse of the medical gases.

Submit
Please wait...
About This Quiz
Medgas100number2 - Quiz

The MEDgas100number2 quiz assesses knowledge on installation and maintenance of medical gas systems. Topics include pipe joint brazing, use of purge gases, and alarm system thresholds, crucial for... see moreprofessionals in healthcare facility management and medical system engineering. see less

2. The presence and correctness of labeling shall be verified.

Explanation

Reference: 5.1.12.3.13

Submit
3. Station inlets for WAGD service shall be legibly marked to identify them and shall be of a type appropriate for the flow and vacuum level required by the facility’s gas anesthetic machines.

Explanation

Station inlets for WAGD service need to be clearly marked for identification purposes and should be suitable for the flow and vacuum level needed by the gas anesthetic machines in the facility. This ensures that the correct gas is being supplied to the machines and that they are functioning properly. Therefore, the statement "Station inlets for WAGD service shall be legibly marked to identify them and shall be of a type appropriate for the flow and vacuum level required by the facility’s gas anesthetic machines" is true.

Submit
4. Where instrument air systems are provided with standby headers, in the event of a compressor failure, the standby header shall automatically serve the system.

Explanation

In instrument air systems where standby headers are present, if a compressor fails, the standby header will automatically take over and supply the system. This means that even if one compressor fails, the system will still have a backup source of air to ensure uninterrupted operation. Therefore, the statement is true.

Submit
5. Compressors for medical air shall be designed to prevent the introduction of contaminants or liquid into the piping system.

Explanation

Compressors for medical air need to be designed in a way that ensures contaminants or liquid cannot enter the piping system. This is crucial for maintaining the purity and safety of the medical air supply, as any contaminants or liquid could potentially harm patients or compromise the effectiveness of medical procedures. Therefore, it is important to have compressors specifically designed to prevent the introduction of such substances into the piping system.

Submit
6. While brazing medical-gas copper joints, a purge gas shall flow continuously to prevent the formation of copper oxide on the inside surface of the joint. What shall be used as a purge gas?

Explanation

Reference: 5.1.10.5.5.1

Submit
7. While brazing medical-gas copper joints, a purge gas shall flow continuously to prevent the formation of copper oxide on the inside surface of the joint. What shall be used as a purge gas?

Explanation

During the brazing process of medical-gas copper joints, a purge gas is required to prevent the formation of copper oxide on the inside surface of the joint. This is because copper oxide can contaminate the joint and compromise its integrity. The ideal purge gas for this purpose should be oil-free and dry to avoid introducing any impurities into the joint. Nitrogen NF (National Formulary) is a high-purity nitrogen gas that meets the required standards for medical applications. It is inert, meaning it does not react with copper or other materials, making it suitable for purging and ensuring a clean joint.

Submit
8. Receivers for medical air shall be equipped with _____________.

Explanation

Receivers for medical air need to be equipped with a relief valve to ensure that the pressure does not exceed safe limits. They also need to have automatic and manual drains to remove any condensate or contaminants that may accumulate in the system. Additionally, a sight glass is necessary to allow visual inspection of the air quality. Therefore, all of the above options are required for receivers of medical air.

Submit
9. Relief valves shall be vented to the ___________, except compressed air systems having less than 3000 cubic feet at STP.

Explanation

Relief valves are designed to release excess pressure in a system to prevent damage or failure. To ensure the safe operation of the relief valve, it is important to vent the released pressure outside the system. This allows the pressure to be safely discharged into the atmosphere, away from any potential hazards or sensitive areas. However, for compressed air systems with a small volume (less than 3000 cubic feet at standard temperature and pressure), venting to the outside may not be necessary as the amount of pressure released is minimal.

Submit
10. All pressure relief valves shall be made of brass, bronze or ____________.

Explanation

Pressure relief valves are an essential component in various systems to prevent overpressure and ensure safety. These valves are subjected to high-pressure conditions, and therefore, they need to be made of materials that can withstand such conditions without corroding or deforming. Brass, bronze, and stainless steel are commonly used materials for pressure relief valves due to their high strength, corrosion resistance, and durability. Carbon steel, cast iron, and copper are not suitable choices for pressure relief valves as they may not possess the required properties to withstand high-pressure conditions. Therefore, stainless steel is the correct answer for the given question.

Submit
11. On system renovations where no piping is changed, functional testing shall be performed to assure no other equipment in the system has been adversely impacted.

Explanation

Reference: 5.1.12.1.12.1

Submit
12. Hangers for copper tube shall be plastic-coated, copper finishes or otherwise insulated from the tube

Explanation

Reference: 5.1.10.10.4.3 (.4)

Submit
13. Each station outlet/inlet for medical gas or vacuum shall be ____________.

Explanation

Each station outlet/inlet for medical gas or vacuum must be gas-specific, meaning that it is designed and designated for a specific type of gas. This ensures that the correct gas is being delivered to the intended location and reduces the risk of accidental mix-ups or cross-contamination. Gas-specific outlets/inlets help maintain the safety and effectiveness of medical gas systems in healthcare facilities.

Submit
14. In a Level 3 vacuum system installed with plastic piping, the pipe shall be polyvinyl chloride (PVC) plastic with a minimum wall thickness of ____________.

Explanation

Reference: 5.3.10.2.3
ANSWERS

Submit
15. When using the autogenous orbital welding process, joints shall be continuously purged inside and outside with an inert gas as qualified with the procedure.

Explanation

Reference: 5.1.10.5.5.12

Submit
16. A signal from each local alarm system shall be connected to the master alarm panels to indicate that a problem is present with the source equipment.

Explanation

Reference: 5.1.9.5.2

Submit
17. Which of the following filler metals shall be used to braze copper-to-copper joints in medical gas/vacuum distribution piping?

Explanation

The BCuP series filler metals should be used to braze copper-to-copper joints in medical gas/vacuum distribution piping.

Submit
18. Tubing for positive pressure medical gas systems delivered from the manufacturer shall be__________________.

Explanation

The tubing for positive pressure medical gas systems delivered from the manufacturer should be plugged or capped to prevent any contamination or leakage. It should also be harddrawn seamless to ensure durability and prevent any cracks or leaks. Additionally, the tubing should be identified as "oxy" or "med" to clearly indicate its purpose and prevent any mix-ups or confusion. Therefore, all of the above options are correct requirements for the tubing of positive pressure medical gas systems.

Submit
19. All valves except zone valve box assemblies shall be ________________.

Explanation

All valves except zone valve box assemblies shall be secured in a secured area, locked or latched, and labeled appropriately. This ensures that the valves are kept in a safe and controlled environment, preventing unauthorized access or tampering. Additionally, labeling the valves appropriately allows for easy identification and maintenance. By implementing all of these measures, the valves can be effectively managed and maintained, ensuring the safety and functionality of the system.

Submit
20. Installers of bulk cryogenic liquid systems shall be qualified to meet CGA M-1 Standard, Guide for Medical Gas Installations at Consumers Sites.

Explanation

The statement is true because according to the given information, installers of bulk cryogenic liquid systems need to be qualified to meet CGA M-1 Standard, which is the Guide for Medical Gas Installations at Consumer Sites. This standard ensures that the installation of these systems is done correctly and safely in medical facilities where cryogenic liquids are used.

Submit
21. Cylinders in use and in storage shall be prevented from reaching temperatures in excess of _______________.

Explanation

Cylinders in use and in storage should be prevented from reaching temperatures in excess of 130º F. This is important because exceeding this temperature can lead to the expansion of gases inside the cylinder, which can cause the cylinder to rupture or explode. It is necessary to maintain a safe temperature range to ensure the integrity and stability of the cylinders and to prevent any potential hazards.

Submit
22. For the initial pressure test, all brazed joints shall be examined for leakage by means of soapy water or other equally effective means that are safe for use with oxygen.

Explanation

Reference: 5.1.12.2.3.6

Submit
23. Which of the following filler metals shall be used to braze copper-to-copper joints in medical gas/vacuum distribution piping?

Explanation

Reference: 5.1.10.5.1.5

Submit
24. Computer systems used as a master alarm shall be continuously attended or shall provide remote signaling of responsible parties through _________. .

Explanation

Reference: 5.1.9.4.1 (2)

Submit
25. All medical gas alarm systems shall have a ____________ audible indication for each condition monitored.

Explanation

Medical gas alarm systems are required to have a cancelable audible indication for each condition monitored. This means that the alarm can be silenced or canceled once the condition being monitored has been resolved or addressed. This feature allows healthcare professionals to acknowledge and respond to the alarm, reducing unnecessary noise and preventing alarm fatigue.

Submit
26. The factory installed tubing on station outlets/inlets shall extend no further than ______ from the body of the terminal.

Explanation

The factory installed tubing on station outlets/inlets should not extend more than 8 inches from the body of the terminal. This is to ensure that the tubing does not become too long and cause any potential hazards or obstructions. By limiting the length to 8 inches, it allows for proper installation and functionality of the terminal without any unnecessary risks.

Submit
27. __________ connectors shall connect the air compressors with their intake and outlet piping.

Explanation

Flexible connectors are used to connect the air compressors with their intake and outlet piping. These connectors are able to absorb vibrations and movements, providing flexibility and preventing damage to the piping system. They allow for easy installation and maintenance, as well as reducing noise and vibration transmission. Therefore, flexible connectors are the most suitable option for connecting air compressors with their intake and outlet piping.

Submit
28. Medical air sources shall be used only for _________ and calibration of medical respiratory devices.

Explanation

Medical air sources are specifically designed and regulated for the purpose of providing clean and safe air for human respiration. Therefore, they should only be used for this purpose and not for operating air-operating devices or for instrument air. Using medical air sources for anything other than human respiration could compromise the quality and safety of the air supply, which is crucial for patients relying on respiratory devices.

Submit
29. Where the Level 3 central supply is remote from the medical gas system use points, the main supply line shall be provided with an emergency shutoff valve so located in the single treatment facility as to be accessible from the use-point location.

Explanation

Reference: 5.3.4.1.2

Submit
30. Area alarms shall be tested to verify the warning signals for all vital life support and critical care areas if the pressure in the piping system increases or decreases by ____________.

Explanation

Reference: 5.1.12.3.5.3

Submit
31. The master alarm system shall activate when the pressure in the main supply lines increase or decrease by __________ percent.

Explanation

The master alarm system is designed to activate when there is a significant change in pressure in the main supply lines. In this case, the correct answer is 20 percent, which means that the alarm will be triggered if the pressure increases or decreases by 20 percent. This threshold ensures that any significant deviations from the normal pressure levels are detected and alerted, allowing for prompt action to be taken to address any potential issues with the supply lines.

Submit
32. Manifolds for gas cylinders without reserve shall consist of ___________ equal headers; each with an average day’s supply, but not fewer than _________ connections.

Explanation

Manifolds for gas cylinders without reserve should consist of two equal headers, each with an average day's supply, but not fewer than two connections. This means that there should be two headers, each capable of supplying enough gas for an average day's usage, and each header should have at least two connections. This ensures that there is redundancy in the system, with two headers providing backup in case one fails, and each header having multiple connections to accommodate the required number of cylinders.

Submit
33. Louvered openings for natural ventilation shall have a minimum free area of __________.

Explanation

Louvered openings for natural ventilation should have a minimum free area of 72 sq. in. This means that the total area of the openings should be at least 72 square inches to allow for sufficient airflow. Having a larger free area ensures better ventilation and allows for more air to enter or exit a space, improving air quality and reducing the risk of stagnant air.

Submit
34. The verifier is required to test the proper operation of the valves installed in each medical gas andvacuum piping system. The verifier is also required to make a list of the rooms or areas controlled by each valve for each gas.

Explanation

Reference: 5.1.12.3.4 (.1)

Submit
35. Area alarm panels for medical gas systems shall indicate when line pressure in the area being monitored increases or decreases by ___________ percent.

Explanation

Reference: 5.1.9.3.2

Submit
36. The quality of the instrument air shall be _________________.

Explanation

The correct answer is "All of the above." This means that the quality of the instrument air should meet all the mentioned criteria, which includes being filtered to .01 micron, free of liquids, and free of hydrocarbon vapors. These requirements ensure that the instrument air is clean and suitable for use in various instruments and systems.

Submit
37. Liquid containers shall have additional product identification visible from all directions with a minimum of _____ inch high letters such as a 360 degree wrap-a-round tape for medical liquid containers.

Explanation

Liquid containers should have additional product identification visible from all directions with a minimum of 2-inch high letters. This is important for ensuring clear and easy identification of the product, especially in medical settings where accuracy and efficiency are crucial. Having the identification visible from all directions helps to prevent any confusion or mistakes in handling or administering the liquid.

Submit
38. Runouts from horizontal mains or branches shall be taken off ________ the centerline of the pipeline.

Explanation

Runouts from horizontal mains or branches should be taken off above the centerline of the pipeline. This is because locating the runouts above the centerline ensures that any air or gas pockets in the pipeline can be easily released. Additionally, taking the runouts off above the centerline helps to prevent the accumulation of sediment or debris in the runouts, which could potentially obstruct the flow of fluid in the pipeline.

Submit
39. Since dew point and carbon monoxide monitors are located upstream of the source valve, demand check fittings are not required.

Explanation

The statement is false because demand check fittings are required for dew point and carbon monoxide monitors, even if they are located upstream of the source valve. Demand check fittings are necessary to ensure proper functioning and accuracy of these monitors.

Submit
40. Carbon monoxide shall activate the required alarms when the CO level exceeds ________.

Explanation

Carbon monoxide shall activate the required alarms when the CO level exceeds 10 ppm. This means that the alarms will only be triggered when the concentration of carbon monoxide in the air reaches or exceeds 10 parts per million. This is an important safety measure as carbon monoxide is a highly toxic gas that can be lethal in high concentrations. By setting the activation threshold at 10 ppm, the alarms will alert individuals to the presence of carbon monoxide before it reaches dangerous levels, allowing them to take immediate action to protect themselves and evacuate if necessary.

Submit
41. Where charcoal filters are required, a colormetric hydrocarbon indicator shall be provided.

Explanation

In situations where charcoal filters are necessary, it is important to have a colormetric hydrocarbon indicator. This indicator helps to detect the presence of hydrocarbons in the air or water that is being filtered. By providing this indicator, it ensures that the filters are effectively removing any harmful hydrocarbons and maintaining the quality of the filtered substance. Therefore, the statement is true.

Submit
42. Level 1 medical air compressors shall be sized to serve the peak calculated demand and in no case shall there be fewer than _____ compressors.

Explanation

Level 1 medical air compressors need to be sized to meet the peak calculated demand. This ensures that there is enough compressed air available for medical procedures. Additionally, there should be a minimum of two compressors to ensure redundancy and prevent any disruptions in the supply of medical air. Having multiple compressors also allows for maintenance and repairs to be carried out on one compressor while the other one continues to provide the necessary air supply.

Submit
43. Bulk cryogenic liquid system sites shall have allowance for at least ____ of clearance around the storage container, vaporizer and the pressure-regulating manifold.

Explanation

Bulk cryogenic liquid systems require a certain amount of clearance around the storage container, vaporizer, and pressure-regulating manifold for safety purposes. The correct answer is 3 feet. This clearance allows for adequate ventilation and prevents any potential hazards or accidents that may occur due to heat buildup or pressure fluctuations. Having a sufficient distance between these components ensures the safe operation of the cryogenic liquid system.

Submit
44. The test required by the installer shall be performed and documented prior to the system verification. The test gas shall be _______________.

Explanation

Reference: 5.1.12.2.1.2

Submit
45. Which group or agency shall review the inspection and testing records prior to the use of all systems to assure that all findings and results of the inspection and testing have been successfully completed?

Explanation

Reference: 5.1.12.1.8

Submit
46. Where shall pressure indicators be provided for medical gas systems?

Explanation

Pressure indicators should be provided for medical gas systems at all of the mentioned locations. This is because pressure indicators are essential for monitoring and maintaining the correct pressure levels in the system. By having pressure indicators on the main supply line, at the area alarm, and on the outlet/inlet side of zone valves, healthcare professionals can easily monitor the pressure levels at different points in the system and ensure that the medical gas supply is safe and reliable.

Submit
47. The scale range of positive pressure analog indicators shall have the normal reading fall within the_________ percentage of the gage scale.

Explanation

The scale range of positive pressure analog indicators should have the normal reading fall within 50% of the gage scale. This means that the midpoint of the scale should represent the normal operating pressure. Having the normal reading fall within 50% of the scale allows for a sufficient range to measure higher or lower pressures without going beyond the limits of the indicator.

Submit
48. A Level 1 dedicated WAGD source shall consist of _____ or more producers, each shall be sufficient to serve the peak calculated demand.

Explanation

A Level 1 dedicated WAGD source shall consist of two or more producers, each sufficient to serve the peak calculated demand. This means that in order to meet the demand for WAGD, there should be at least two producers available. Having only one producer may not be enough to meet the peak demand. Therefore, the correct answer is Two.

Submit
49. The compressor air intakes shall be located outdoors above roof level at a minimum distance of__________ above the ground.

Explanation

The compressor air intakes should be located outdoors above roof level to ensure that they are not affected by any obstructions or contaminants present at ground level. Placing them at a minimum distance of 20 ft above the ground helps to prevent the intake of dust, debris, and other pollutants that could potentially damage the compressor and affect its performance. This height also allows for proper air circulation and reduces the risk of any potential hazards.

Submit
50. An in-building emergency reserve system can be substituted for the EOSC.

Explanation

An in-building emergency reserve system can be substituted for the EOSC. This means that instead of relying on the EOSC (Emergency Operations and Control System), the in-building emergency reserve system can be used as an alternative. This suggests that the in-building emergency reserve system is capable of performing the same functions and providing the same level of emergency response as the EOSC.

Submit
51. Manifolds for cryogenic liquid cylinders shall consist of __________ equal headers; each having sufficient number of liquid containers for an average day’s supply.

Explanation

Manifolds for cryogenic liquid cylinders shall consist of 2 equal headers; each having sufficient number of liquid containers for an average day’s supply. This means that there will be two headers in the manifold system, with each header having enough liquid containers to meet the average daily demand. This setup allows for efficient distribution and supply of cryogenic liquids.

Submit
52. Which of the following hazards shall be considered in the design, installation, testing and maintenance of medical gas and vacuum piping systems?

Explanation

In the design, installation, testing, and maintenance of medical gas and vacuum piping systems, it is crucial to consider the hazard of fire and explosions. This is because these systems involve the transportation of gases that can be highly flammable or explosive if not handled properly. By taking fire and explosion hazards into account, appropriate safety measures can be implemented to prevent accidents and ensure the safety of both patients and medical staff.

Submit
53. The installation of medical gas and vacuum systems shall be made by experienced, qualified and competent installers. The installers shall meet the requirements of __________________.

Explanation

Reference: 5.1.10.10.11.2

Submit
54. Runouts from horizontal piping shall be taken off above the centerline of the pipeline shall rise vertically or at an angle of not less than __________ degrees vertically.

Explanation

The correct answer is 45 degrees. When taking a runout from horizontal piping, it is important to ensure that it rises vertically or at an angle of not less than 45 degrees vertically. This is necessary to prevent any potential backflow or blockage in the pipeline. A 45-degree angle allows for proper drainage and flow of the fluid or material in the pipeline.

Submit
55. The scale range of positive pressure analog indicators shall have the normal reading fall within the _________ percentage of the gauge scale.

Explanation

Reference: 5.1.8.1.3

Submit
56. A shutoff valve shall be placed at the immediate connection of each source system to the distribution piping system. What is the name given to the valve?

Explanation

The valve referred to in the question is called the "source" valve. This valve is placed at the immediate connection of each source system to the distribution piping system. It is responsible for shutting off the flow of fluid or gas from the source system into the distribution system.

Submit
57. Medical air purity for compressor systems shall be analyzed prior to the source valve being opened. Samples taken at the system sample port for carbon monoxide shall not exceed _____________.

Explanation

Reference: 5.1.12.3.12.3

Submit
58. All master, area and local alarm systems shall include separate _________ and _______ indicators for each condition monitored.

Explanation

Referance 5.1.9.1 (1) (3)

Submit
59. What is the name given to the shutoff valve installed on all lateral branch piping from a main or riser?

Explanation

The shutoff valve installed on all lateral branch piping from a main or riser is called a service valve. This valve allows for the control and regulation of water flow to specific areas or zones, making it an essential component in plumbing systems.

Submit
60. Level 3 air sources for a compressor located inside shall meet which, if any, of the following requirements?

Explanation

Reference: 5.3.3.5.7.1 (1) (2)

Submit
61. Pipe labels shall be located at intervals of not more than __________ ft.

Explanation

Reference: 5.1.11.1.2 (1)

Submit
62. Threaded joints in medical gas and vacuum distribution piping shall be limited to __________.

Explanation

Reference: 5.1.10.4 (1)

Submit
63. In positive pressure systems, area alarm sensors for vital life support and critical care areas shall be located on which side of the zone valve box assemblies

Explanation

Reference: 5.1.9.3.4 (1)

Submit
64. Which of the following systems shall not be permitted to be located in the same indoor enclosure?

Explanation

A bulk cryogenic liquid system should not be permitted to be located in the same indoor enclosure as the other systems mentioned. This is because bulk cryogenic liquid systems involve storing and handling large quantities of extremely cold liquids, such as liquid nitrogen or liquid oxygen. These systems require specialized storage and safety measures, including insulation and ventilation, to prevent the risk of leaks, spills, or explosions. Co-locating a bulk cryogenic liquid system with other systems could increase the risk of accidents and compromise the safety of the overall facility.

Submit
65. In positive pressure systems, area alarm sensors for vital life support and critical care areas shall be located on which side of the zone valve box assemblies?

Explanation

In positive pressure systems, area alarm sensors for vital life support and critical care areas are required to be located on all sides of the zone valve box assemblies. This ensures that any change in pressure or flow within the system can be accurately detected and monitored from all angles. By having sensors on the patient room side, outlet/inlet side, and downstream side of the zone valve box assemblies, any potential issues or malfunctions can be quickly identified and addressed, ensuring the safety and well-being of the patients in these areas.

Submit
66. Vacuum receivers shall be capable of withstanding a gage vacuum of ________ inches of mercury.

Explanation

Vacuum receivers need to be able to withstand a gage vacuum of 29.9 inches of mercury. This is the correct answer because it is the closest option to the standard atmospheric pressure at sea level, which is 29.92 inches of mercury. A vacuum receiver must be able to handle this level of vacuum to effectively function in various applications.

Submit
67. Level 1 medical-surgical vacuum sources shall consist of an automatic means to prevent_____________ through any off-cycle vacuum pump.

Explanation

Level 1 medical-surgical vacuum sources need to have an automatic means to prevent backflow through any off-cycle vacuum pump. Backflow refers to the reverse flow of fluids or gases, which can be harmful in a medical setting. By preventing backflow, the vacuum system ensures the proper functioning and safety of the equipment and maintains a clean and sterile environment.

Submit
68. Mains, branches and drops to individual service outlets/inlets in Level 3 gas powered and vacuum piping systems shall not be the same as the sizes used for oxygen and nitrous oxide.

Explanation

Reference: 5.3.10.10.3.3

Submit
69. Joints shall be brazed within _______ hours after the surfaces are cleaned for brazing.

Explanation

Reference: 5.1.10.5.3.13

Submit
70. The master alarm system shall consist of two or more alarm panels, a centralized computer system shall not be permitted to be used as a substitute for one of the required master alarm panels.

Explanation

The statement is false because it states that a centralized computer system cannot be used as a substitute for one of the required master alarm panels.

Submit
71. Where the bulk cryogenic liquid oxygen supply system is outside of and remote from the building served, a _________ connection shall be installed.  

Explanation

In situations where the bulk cryogenic liquid oxygen supply system is located outside of and far away from the building it serves, it is necessary to install an emergency oxygen supply connection. This connection ensures that there is a backup source of oxygen available in case of any emergencies or disruptions in the main supply system. This is important for the safety and well-being of the occupants of the building, as it ensures that there is always a reliable source of oxygen available, even in unforeseen circumstances.

Submit
72. Brazed joints shall be made using a brazing alloy that exhibits a melting temperature in excess of________________ to retain the integrity of the piping system in the event of fire.

Explanation

Reference: 5.1.10.5.1.1

Submit
73. Where medical air piping systems at different operating pressures are required, the piping shall separate after the __________.

Explanation

In medical air piping systems, filters are used to remove impurities and contaminants from the air. Since different operating pressures may be required for different parts of the system, it is necessary to separate the piping after the filters. This allows for the appropriate pressure regulation and distribution of clean air to various areas of the system.

Submit
74. Manifolds for cryogenic liquid cylinders shall indicate when or at a predetermined set point before the reserve contents fall to one day’s average supply, indicating _______.

Explanation

The correct answer is "Reserve low." Manifolds for cryogenic liquid cylinders need to indicate when the reserve contents are approaching a level that is one day's average supply. This indication is important to ensure that the reserve does not run out completely and to allow for timely replenishment. Therefore, the term "Reserve low" accurately describes the situation where the reserve contents are nearing a critical level.

Submit
75. Instrument air systems shall be permitted to interconnect with medical air systems that have at least two or more compressors.

Explanation

Instrument air systems should not be interconnected with medical air systems, even if the medical air systems have multiple compressors. This is because instrument air systems may contain contaminants or impurities that can be harmful if they come into contact with medical equipment or patients. Therefore, it is important to keep these systems separate to ensure the safety and integrity of the medical air supply.

Submit
76. If dryers, filters and regulators are sized to serve the peak calculated demand, they shall not be duplexed.

Explanation

Dryers, filters, and regulators are typically sized to serve the peak calculated demand in order to ensure that they can handle the maximum load. However, duplexing refers to the practice of having two identical units operating in parallel, providing redundancy and backup in case of failure. Therefore, if the equipment is sized to serve the peak demand, it can still be duplexed to provide additional reliability and backup. Hence, the statement "If dryers, filters and regulators are sized to serve the peak calculated demand, they shall not be duplexed" is false.

Submit
77. Underground piping buried outside of buildings shall be installed below the local level of frost penetration and shall be protected by a _____________.

Explanation

Reference: 5.1.10.10.5.3

Submit
78. The master alarm system shall consist of two or more alarm panels, a centralized computer system shall not be permitted to be used as a substitute for one of the required master alarm panels.

Explanation

Reference: 5.1.9.2.2

Submit
79. One of the master alarm panels shall be located in the office or work space of the individual responsible for the maintenance of the medical gas piping system. Where shall the other alarm be located?  

Explanation

Reference: 5.1.9.2.1 (2)

Submit
80. Piping for Level 3 positive-pressure medical gases shall be cleaned for oxygen service, delivered plugged or capped and shall be hard-drawn, seamless copper ASTM _______.

Explanation

Reference: 5.3.10.1.1.4

Submit
81. What is required of the alarm system if another alarm condition occurs while the audible alarm is silenced?

Explanation

Reference: 5.1.9.1 (8)

Submit
82. What is the minimum number of compressors required in an instrument air system that employs a standby header?

Explanation

In an instrument air system that employs a standby header, only one compressor is required. The standby header serves as a backup in case the primary header fails. Therefore, even if one compressor is not functioning, the system can still operate with the standby header. Having multiple compressors would provide additional redundancy, but the minimum requirement is one compressor.

Submit
83. When nitrogen is used as the gas in a reserves/supplement to a Level 3 compressor source, the nitrogen gas cylinders shall be permitted to be stored in the compressor room.

Explanation

Reference: 5.3.3.5.8.6 (2)

Submit
84. A continuous tape or marker shall be placed immediately above the buried pipeline enclosure and shall be identified by _____________.

Explanation

Reference: 5.1.10.10.5.8

Submit
85. Where liquid ring compressors are used, air receivers shall be equipped with a high water level sensor that activates a(n) ________________ alarm indicator.

Explanation

In applications where liquid ring compressors are used, air receivers should have a high water level sensor that activates a local alarm indicator. This means that the alarm indicator will be located in close proximity to the air receiver, allowing for immediate notification and response in case of a high water level. This ensures that any potential issues with the liquid ring compressor can be addressed promptly and effectively.

Submit
86. The master alarm system shall activate when the main line of the vacuum system drops to or below________________.

Explanation

Reference: 5.1.9.2.4 (8)

Submit
87. Mains, branches and drops to individual service outlets in Level 3 oxygen piping systems shall be not less than _____________.

Explanation

Reference: 5.3.10.10.3.1

Submit
88. Instrument air dew point shall indicate at the local site when the line pressure dew point is greater than _____________.

Explanation

Reference: 5.1.9.5.4 (6)

Submit
89. Mains, branches and drops to individual service outlets for Level 3 nitrous oxide shall be not less than____________.

Explanation

Reference: 5.3.10.10.3.2

Submit
90. The standing pressure test for positive pressure medical gas piping shall be conducted with the source valve closed and the piping system subjected to a pressure of _____________.

Explanation

Reference: 5.1.12.2.6.3 (.4)

Submit
91. Verification testing shall be conducted by a party who is technically competent and experienced in the field of medical gas and vacuum pipeline testing, and meets the requirements of _________________.

Explanation

Reference: 5.1.12.3.1.3

Submit
92. What percent of the zones shall be tested at the outlet most remote from the source to verify the piping particulate test?

Explanation

Reference: 5.1.12.3.7.2

Submit
93. Which of the following filler metals shall be used when brazing dissimilar metals such as copper and bronze or brass?

Explanation

Reference: 5.1.10.5.4.1

Submit
94. The standing pressure test for vacuum systems shall be conducted after installation of all components and the piping system shall be subjected to a test pressure of _____________________.

Explanation

Reference: 5.1.12.2.7.3

Submit
95. System verification shall be performed by a party other than the installing contractor, except if the system has been installed by in-house personnel, in which case the verification shall be permitted by the personnel of that organization who meet the requirements of ASSE Standard 6010.

Explanation

Reference: 5.1.12.3.1.5

Submit
96. Brazing procedures and brazer performance for the installation of medical gas and vacuum piping shall be qualified in accordance with _______________.

Explanation

Reference: 5.1.10.10.12.1

Submit
97. The pressure in the main line of each medical gas system, the operation and condition of the source of supply and the reserve source (if any) shall be monitored at the _____________ alarm.

Explanation

Reference: 5.1.9.2

Submit
98. All alarm systems shall be tested monthly for lamp or LED failure.

Explanation

Reference: 5.1.9.1 (4)

Submit
99. A Level 3 warning system for medical gases shall provide a master, area and local alarm system.

Explanation

Reference: 5.3.9.1 (1)

Submit
100. In a cylinder supplied medical gas system with reserve, which alarm system(s) will activate when, or just before, the changeover to the reserve supply occurs?

Explanation

When the changeover to the reserve supply occurs in a cylinder supplied medical gas system with reserve, the Master alarm system will activate. This alarm system is designed to alert the users or operators of the system about the switch to the reserve supply. It ensures that they are aware of the change and can take appropriate actions if necessary. The Local and Area alarm systems may also activate, but the Master alarm system is specifically mentioned as the one that will definitely activate during the changeover.

Submit
View My Results

Quiz Review Timeline (Updated): Mar 21, 2023 +

Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.

  • Current Version
  • Mar 21, 2023
    Quiz Edited by
    ProProfs Editorial Team
  • Nov 08, 2010
    Quiz Created by
    Pbarton
Cancel
  • All
    All (100)
  • Unanswered
    Unanswered ()
  • Answered
    Answered ()
Locations for central supply systems and the storage of medical gases...
The presence and correctness of labeling shall be verified.
Station inlets for WAGD service shall be legibly marked to identify...
Where instrument air systems are provided with standby headers, in the...
Compressors for medical air shall be designed to prevent the...
While brazing medical-gas copper joints, a purge gas shall flow...
While brazing medical-gas copper joints, a purge gas shall flow...
Receivers for medical air shall be equipped with _____________.
Relief valves shall be vented to the ___________, except compressed...
All pressure relief valves shall be made of brass, bronze or...
On system renovations where no piping is changed, functional testing...
Hangers for copper tube shall be plastic-coated, copper finishes or...
Each station outlet/inlet for medical gas or vacuum shall be...
In a Level 3 vacuum system installed with plastic piping, the pipe...
When using the autogenous orbital welding process, joints shall be...
A signal from each local alarm system shall be connected to the master...
Which of the following filler metals shall be used to braze...
Tubing for positive pressure medical gas systems delivered from the...
All valves except zone valve box assemblies shall be ________________.
Installers of bulk cryogenic liquid systems shall be qualified to meet...
Cylinders in use and in storage shall be prevented from reaching...
For the initial pressure test, all brazed joints shall be examined for...
Which of the following filler metals shall be used to braze...
Computer systems used as a master alarm shall be continuously attended...
All medical gas alarm systems shall have a ____________ audible...
The factory installed tubing on station outlets/inlets shall extend no...
__________ connectors shall connect the air compressors with their...
Medical air sources shall be used only for _________ and calibration...
Where the Level 3 central supply is remote from the medical gas system...
Area alarms shall be tested to verify the warning signals for all...
The master alarm system shall activate when the pressure in the main...
Manifolds for gas cylinders without reserve shall consist of...
Louvered openings for natural ventilation shall have a minimum free...
The verifier is required to test the proper operation of the valves...
Area alarm panels for medical gas systems shall indicate when line...
The quality of the instrument air shall be _________________.
Liquid containers shall have additional product identification visible...
Runouts from horizontal mains or branches shall be taken off ________...
Since dew point and carbon monoxide monitors are located upstream of...
Carbon monoxide shall activate the required alarms when the CO level...
Where charcoal filters are required, a colormetric hydrocarbon...
Level 1 medical air compressors shall be sized to serve the peak...
Bulk cryogenic liquid system sites shall have allowance for at least...
The test required by the installer shall be performed and documented...
Which group or agency shall review the inspection and testing records...
Where shall pressure indicators be provided for medical gas systems?
The scale range of positive pressure analog indicators shall have the...
A Level 1 dedicated WAGD source shall consist of _____ or more...
The compressor air intakes shall be located outdoors above roof level...
An in-building emergency reserve system can be substituted for the...
Manifolds for cryogenic liquid cylinders shall consist of __________...
Which of the following hazards shall be considered in the design,...
The installation of medical gas and vacuum systems shall be made by...
Runouts from horizontal piping shall be taken off above the centerline...
The scale range of positive pressure analog indicators shall have the...
A shutoff valve shall be placed at the immediate connection of each...
Medical air purity for compressor systems shall be analyzed prior to...
All master, area and local alarm systems shall include separate...
What is the name given to the shutoff valve installed on all lateral...
Level 3 air sources for a compressor located inside shall meet which,...
Pipe labels shall be located at intervals of not more than __________...
Threaded joints in medical gas and vacuum distribution piping shall be...
In positive pressure systems, area alarm sensors for vital life...
Which of the following systems shall not be permitted to be located in...
In positive pressure systems, area alarm sensors for vital life...
Vacuum receivers shall be capable of withstanding a gage vacuum of...
Level 1 medical-surgical vacuum sources shall consist of an automatic...
Mains, branches and drops to individual service outlets/inlets in...
Joints shall be brazed within _______ hours after the surfaces are...
The master alarm system shall consist of two or more alarm panels, a...
Where the bulk cryogenic liquid oxygen supply system is outside of and...
Brazed joints shall be made using a brazing alloy that exhibits a...
Where medical air piping systems at different operating pressures are...
Manifolds for cryogenic liquid cylinders shall indicate when or at a...
Instrument air systems shall be permitted to interconnect with medical...
If dryers, filters and regulators are sized to serve the peak...
Underground piping buried outside of buildings shall be installed...
The master alarm system shall consist of two or more alarm panels, a...
One of the master alarm panels shall be located in the office or work...
Piping for Level 3 positive-pressure medical gases shall be cleaned...
What is required of the alarm system if another alarm condition occurs...
What is the minimum number of compressors required in an instrument...
When nitrogen is used as the gas in a reserves/supplement to a Level 3...
A continuous tape or marker shall be placed immediately above the...
Where liquid ring compressors are used, air receivers shall be...
The master alarm system shall activate when the main line of the...
Mains, branches and drops to individual service outlets in Level 3...
Instrument air dew point shall indicate at the local site when the...
Mains, branches and drops to individual service outlets for Level 3...
The standing pressure test for positive pressure medical gas piping...
Verification testing shall be conducted by a party who is technically...
What percent of the zones shall be tested at the outlet most remote...
Which of the following filler metals shall be used when brazing...
The standing pressure test for vacuum systems shall be conducted after...
System verification shall be performed by a party other than the...
Brazing procedures and brazer performance for the installation of...
The pressure in the main line of each medical gas system, the...
All alarm systems shall be tested monthly for lamp or LED failure.
A Level 3 warning system for medical gases shall provide a master,...
In a cylinder supplied medical gas system with reserve, which alarm...
Alert!

Advertisement