Locations for central supply systems and the storage of medical gases...
The presence and correctness of labeling shall be verified.
Station inlets for WAGD service shall be legibly marked to identify...
Where instrument air systems are provided with standby headers, in the...
Compressors for medical air shall be designed to prevent the...
While brazing medical-gas copper joints, a purge gas shall flow...
While brazing medical-gas copper joints, a purge gas shall flow...
Receivers for medical air shall be equipped with _____________.
Relief valves shall be vented to the ___________, except compressed...
All pressure relief valves shall be made of brass, bronze or...
On system renovations where no piping is changed, functional testing...
Hangers for copper tube shall be plastic-coated, copper finishes or...
Each station outlet/inlet for medical gas or vacuum shall be...
In a Level 3 vacuum system installed with plastic piping, the pipe...
When using the autogenous orbital welding process, joints shall be...
A signal from each local alarm system shall be connected to the master...
Which of the following filler metals shall be used to braze...
Tubing for positive pressure medical gas systems delivered from the...
All valves except zone valve box assemblies shall be ________________.
Installers of bulk cryogenic liquid systems shall be qualified to meet...
Cylinders in use and in storage shall be prevented from reaching...
For the initial pressure test, all brazed joints shall be examined for...
Which of the following filler metals shall be used to braze...
Computer systems used as a master alarm shall be continuously attended...
All medical gas alarm systems shall have a ____________ audible...
The factory installed tubing on station outlets/inlets shall extend no...
__________ connectors shall connect the air compressors with their...
Medical air sources shall be used only for _________ and calibration...
Where the Level 3 central supply is remote from the medical gas system...
Area alarms shall be tested to verify the warning signals for all...
The master alarm system shall activate when the pressure in the main...
Manifolds for gas cylinders without reserve shall consist of...
Louvered openings for natural ventilation shall have a minimum free...
The verifier is required to test the proper operation of the valves...
Area alarm panels for medical gas systems shall indicate when line...
The quality of the instrument air shall be _________________.
Liquid containers shall have additional product identification visible...
Runouts from horizontal mains or branches shall be taken off ________...
Since dew point and carbon monoxide monitors are located upstream of...
Carbon monoxide shall activate the required alarms when the CO level...
Where charcoal filters are required, a colormetric hydrocarbon...
Level 1 medical air compressors shall be sized to serve the peak...
Bulk cryogenic liquid system sites shall have allowance for at least...
The test required by the installer shall be performed and documented...
Which group or agency shall review the inspection and testing records...
Where shall pressure indicators be provided for medical gas systems?
The scale range of positive pressure analog indicators shall have the...
A Level 1 dedicated WAGD source shall consist of _____ or more...
The compressor air intakes shall be located outdoors above roof level...
An in-building emergency reserve system can be substituted for the...
Manifolds for cryogenic liquid cylinders shall consist of __________...
Which of the following hazards shall be considered in the design,...
The installation of medical gas and vacuum systems shall be made by...
Runouts from horizontal piping shall be taken off above the centerline...
The scale range of positive pressure analog indicators shall have the...
A shutoff valve shall be placed at the immediate connection of each...
Medical air purity for compressor systems shall be analyzed prior to...
All master, area and local alarm systems shall include separate...
What is the name given to the shutoff valve installed on all lateral...
Level 3 air sources for a compressor located inside shall meet which,...
Pipe labels shall be located at intervals of not more than __________...
Threaded joints in medical gas and vacuum distribution piping shall be...
In positive pressure systems, area alarm sensors for vital life...
Which of the following systems shall not be permitted to be located in...
In positive pressure systems, area alarm sensors for vital life...
Vacuum receivers shall be capable of withstanding a gage vacuum of...
Level 1 medical-surgical vacuum sources shall consist of an automatic...
Mains, branches and drops to individual service outlets/inlets in...
Joints shall be brazed within _______ hours after the surfaces are...
The master alarm system shall consist of two or more alarm panels, a...
Where the bulk cryogenic liquid oxygen supply system is outside of and...
Brazed joints shall be made using a brazing alloy that exhibits a...
Where medical air piping systems at different operating pressures are...
Manifolds for cryogenic liquid cylinders shall indicate when or at a...
Instrument air systems shall be permitted to interconnect with medical...
If dryers, filters and regulators are sized to serve the peak...
Underground piping buried outside of buildings shall be installed...
The master alarm system shall consist of two or more alarm panels, a...
One of the master alarm panels shall be located in the office or work...
Piping for Level 3 positive-pressure medical gases shall be cleaned...
What is required of the alarm system if another alarm condition occurs...
What is the minimum number of compressors required in an instrument...
When nitrogen is used as the gas in a reserves/supplement to a Level 3...
A continuous tape or marker shall be placed immediately above the...
Where liquid ring compressors are used, air receivers shall be...
The master alarm system shall activate when the main line of the...
Mains, branches and drops to individual service outlets in Level 3...
Instrument air dew point shall indicate at the local site when the...
Mains, branches and drops to individual service outlets for Level 3...
The standing pressure test for positive pressure medical gas piping...
Verification testing shall be conducted by a party who is technically...
What percent of the zones shall be tested at the outlet most remote...
Which of the following filler metals shall be used when brazing...
The standing pressure test for vacuum systems shall be conducted after...
System verification shall be performed by a party other than the...
Brazing procedures and brazer performance for the installation of...
The pressure in the main line of each medical gas system, the...
All alarm systems shall be tested monthly for lamp or LED failure.
A Level 3 warning system for medical gases shall provide a master,...
In a cylinder supplied medical gas system with reserve, which alarm...