The ProProfs editorial team is comprised of experienced subject matter experts. They've collectively created over 10,000 quizzes and lessons, serving over 100 million users. Our team includes in-house content moderators and subject matter experts, as well as a global network of rigorously trained contributors. All adhere to our comprehensive editorial guidelines, ensuring the delivery of high-quality content.
Learn about Our Editorial Process
| By NCFMA
N
NCFMA
Community Contributor
Quizzes Created: 5 | Total Attempts: 20,912
| Attempts: 9,858 | Questions: 100
Please wait...
Question 1 / 100
0 %
0/100
Score 0/100
1. The ____________, upon finding any overcrowding conditions above the approved capacity or obstructions in aisles, passageways or other means of egress, or upon finding any condition which constitutes a life safety hazard in a building, shall be authorized to cause the event to be stopped until such condition or obstructed is corrected.

Explanation

The Fire Code Official is the correct answer because they have the authority to stop an event if they find overcrowding conditions, obstructions in aisles or passageways, or any other condition that poses a life safety hazard in a building. They are responsible for enforcing fire safety regulations and ensuring that buildings comply with the approved capacity and safety standards.

Submit
Please wait...
About This Quiz
IFC Fire Inspector Exam: Hardest Quiz! - Quiz

This State Certification Exam for Fire Inspector Level 1 is based upon the International Fire Code with North Carolina amendments. The International Fire Code quiz(IFC) is designed... see moreto recognize hazards related to fire, explosion, or hazardous materials. There is a list of 93 questions with multiple-choice options. Read the questions carefully and answer.
see less

2. Exits shall discharge directly to ___________ of the building.

Explanation

Exits shall discharge directly to the exterior of the building in order to provide a safe and efficient means of egress during emergencies. Direct access to the exterior allows occupants to quickly evacuate the building and reach a safe location outside. This also helps to prevent congestion and delays that may occur if exits discharge to interior spaces or corridors. By discharging directly to the exterior, occupants can easily access emergency services and avoid potential hazards within the building.

Submit
3. Portable electric heaters, of all types, are __________ in any daycare.

Explanation

603.5.3 P55-56

Submit
4. Commercial cooking equipment using animal or vegetable oils shall be protected with a _______ rated portable fire extinguisher.

Explanation

Commercial cooking equipment using animal or vegetable oils shall be protected with a Class K rated portable fire extinguisher. Class K fire extinguishers are specifically designed and effective for extinguishing fires involving cooking oils and fats. These extinguishers use a special agent that reacts with the oils to form a soapy foam, which helps to cool and smother the fire. Using a Class K extinguisher is essential in commercial kitchens to ensure the safety of both the workers and the property.

Submit
5. Unvented, portable fuel-fired heating equipment is prohibited in ___ occupancies.

Explanation

Unvented, portable fuel-fired heating equipment is prohibited in all occupancies. This means that it is not allowed in any type of building or space, whether it is residential (R1, R2, R3, R4), commercial (C), industrial (I), or any other type of occupancy. The reason for this prohibition is likely due to the potential dangers and risks associated with using unvented fuel-fired heating equipment, such as the release of carbon monoxide and other harmful gases. To ensure the safety of occupants, it is important to use properly vented heating equipment in all occupancies.

Submit
6. Where _______, unattended self-service station is permitted.

Explanation

The word "permitted" suggests that there are certain rules or regulations in place regarding the use of the self-service station. The word "approved" implies that these rules have been reviewed and authorized by the relevant authority, allowing the use of the self-service station. Therefore, "approved" is the correct answer as it aligns with the idea of the station being allowed or authorized.

Submit
7. An outdoor fire, for ceremonial purpose having a fuel diameter area of 3 feet or less and a height of 2 feet or less, is a/an _______________.

Explanation

A recreational fire is a suitable explanation for an outdoor fire used for ceremonial purposes with a fuel diameter area of 3 feet or less and a height of 2 feet or less. This type of fire is typically small and controlled, intended for enjoyment and socializing rather than waste disposal or burning rubbish.

Submit
8. A device, which has the appearance of life safety or fire protection equipment, but does not perform that function, shall be ___________.

Explanation

A device that resembles life safety or fire protection equipment but does not actually serve that purpose should be prohibited. This is because such a device can mislead people into thinking that they are protected in case of an emergency, when in reality they are not. Prohibiting the use of such devices ensures that proper safety measures are in place and that people are not put at risk due to false appearances.

Submit
9. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested _________ to confirm proper operation and full closure.

Explanation

The correct answer is annually because fire doors need to be inspected and tested regularly to ensure that they are functioning properly and can fully close. Annual inspections and tests are necessary to identify any issues or malfunctions that may have occurred over time and to address them promptly to maintain the fire safety standards of the building. Regular inspections also help to prevent any potential fire hazards and ensure the overall effectiveness of the fire doors in case of an emergency.

Submit
10. An enclosed or separated space within a building, where hazardous chemical storage does not exceed maximum allowable quantities is a ____________.

Explanation

A control area is an enclosed or separated space within a building where hazardous chemical storage does not exceed maximum allowable quantities. It is a designated area that is specifically designed and equipped to safely store and handle hazardous materials. Control areas are implemented to minimize the risk of accidents and ensure the safety of individuals working in the building.

Submit
11. Horizontal sliding fire doors shall be tested _______ to confirm proper operation.

Explanation

Horizontal sliding fire doors should be tested annually to ensure that they are functioning properly. Regular testing is necessary to ensure that the doors can effectively contain and prevent the spread of fire in the event of an emergency. By conducting annual tests, any issues or malfunctions can be identified and addressed promptly, ensuring the safety of the building and its occupants.

Submit
12. The required turning radius of a fire apparatus road shall be determined by the _____________.

Explanation

The required turning radius of a fire apparatus road is determined by the Fire Code Official. This official is responsible for enforcing fire safety regulations and ensuring that fire apparatus can access the site effectively. They have the knowledge and authority to determine the necessary specifications for the turning radius based on the specific requirements and guidelines outlined in the fire code.

Submit
13. When fire door hold open devices in Fire-Resistant-Rated buildings, are inoperative, the door shall be_________.

Explanation

When fire door hold open devices in Fire-Resistant-Rated buildings are inoperative, it is important to keep the door closed. This is because fire doors are designed to prevent the spread of fire and smoke in the event of a fire. By keeping the door closed, it helps to maintain the integrity of the fire-resistant barrier and ensures that the fire does not easily pass through the door.

Submit
14. Required fire walls, fire barriers, and fire partitions shall be ___________ to prevent the passage of fire.

Explanation

Fire walls, fire barriers, and fire partitions are designed to prevent the passage of fire and protect occupants and property. However, over time, these fire protection measures can become damaged or compromised. Therefore, it is crucial to regularly inspect and maintain them to ensure their effectiveness in preventing the spread of fire. This includes repairing any damage, replacing worn-out components, and ensuring that they are in compliance with fire safety regulations. By keeping these fire protection systems well-maintained, the risk of fire spreading can be significantly reduced.

Submit
15. How many chock blocks are required on a gasoline transport tanker?

Explanation

A gasoline transport tanker typically requires two chock blocks. Chock blocks are used to prevent the tanker from rolling or moving while it is parked or during loading and unloading. Placing chock blocks on both sides of the tanker helps to ensure stability and safety.

Submit
16. When is a repair garage required to have a sprinkler system?

Explanation

A repair garage is required to have a sprinkler system when any of the conditions mentioned in the options are met. This means that if the garage has more than 2 stories, or if it exceeds 12,000 square feet in size, or if it is located in a basement, then it must have a sprinkler system. The presence of any one of these conditions would necessitate the installation of a sprinkler system for safety purposes.

Submit
17. The ____________ or the fire department official in charge of an incident shall be authorized order the evacuation of any building, in which there exists any life-threatening hazard to the occupants.

Explanation

The Fire Code Official is the correct answer because they are responsible for enforcing fire safety regulations and ensuring compliance with the fire code. In the event of a life-threatening hazard in a building, it is within their authority to order an evacuation to protect the occupants. The Fire Code Official has the expertise and knowledge to assess the situation and make the necessary decisions to ensure the safety of the individuals involved.

Submit
18. Class III standpipe systems shall be installed when the lowest floor level is ____ feet or more above the lowest level of fire department access.

Explanation

Class III standpipe systems are required to be installed when the lowest floor level is 30 feet or more above the lowest level of fire department access. This is because Class III standpipe systems are designed to provide a means for firefighters to access water on higher floors of a building during a fire incident. By requiring the installation of these systems when the lowest floor level is 30 feet or more above the lowest level of fire department access, it ensures that firefighters have a reliable water source to combat fires in tall buildings.

Submit
19. Which of the following structures is/are exempt from the requirements of this code?

Explanation

All of the structures mentioned in the options are exempt from the requirements of the code. This means that they are not subject to the regulations and standards set forth in the code. One and two-family residential buildings, barns on farms outside municipalities, and utility poles are all exempt from the requirements of the code.

Submit
20. Fuel dispensing devices shall be _____________ the attendant at all times.

Explanation

Fuel dispensing devices should be in clear view of the attendant at all times. This is important for safety reasons as it allows the attendant to monitor the fueling process and quickly respond to any emergencies or malfunctions. Having the devices in clear view ensures that the attendant can easily observe and control the fueling operation, minimizing the risk of accidents or spills.

Submit
21. Class III standpipe systems shall be installed when the lowest floor level is ____ feet or more above the lowest level of fire department access.

Explanation

Class III standpipe systems shall be installed when the lowest floor level is 30 feet or more above the lowest level of fire department access. This means that if the lowest floor level of a building is 30 feet or higher above the level at which the fire department can access the building, a Class III standpipe system must be installed. This system provides a means for firefighters to access water on higher floors in the event of a fire, allowing them to effectively combat the fire and protect the building and its occupants.

Submit
22. Fire safety and evacuation plans shall be reviewed or updated _________ or as necessary.

Explanation

Fire safety and evacuation plans need to be regularly reviewed or updated to ensure their effectiveness and compliance with any changes in regulations or the building's layout. The most suitable frequency for this review is annually, as it strikes a balance between being proactive in identifying any necessary updates and not overwhelming the staff with too frequent reviews. This timeframe allows for sufficient time to gather feedback, make any necessary changes, and communicate them to all relevant personnel.

Submit
23. A code official may extend any permit for a period not to exceed ______ days.

Explanation

A code official may extend any permit for a period not to exceed 180 days. This means that if there is a need for an extension on a permit, the code official can grant a maximum extension of 180 days. This allows for flexibility in case there are delays or unforeseen circumstances that prevent the completion of the project within the original permit timeframe.

Submit
24. The fire code requirement, for Liquefied Petroleum Gases (LPG) tank installation inspections, is the responsibility of _______________.

Explanation

The correct answer is the NC Department of Agriculture. The NC Department of Agriculture is responsible for conducting inspections and enforcing regulations related to the installation of Liquefied Petroleum Gases (LPG) tanks. They ensure that proper safety measures are in place to prevent fire hazards and protect the public.

Submit
25. Exterior lumber piles shall not exceed ____ feet in height.

Explanation

Exterior lumber piles should not exceed 20 feet in height. This limitation is likely in place to ensure the stability and safety of the lumber piles. Higher piles may pose a risk of collapse or instability, which could result in accidents or damage to property. By setting a maximum height of 20 feet, it helps to maintain a manageable and safe working environment.

Submit
26. What commodity class, for high piled combustible storage, are foam rubber mattresses?

Explanation

Foam rubber mattresses are classified as high hazard for high piled combustible storage. This means that they have a high potential for combustion and can contribute to the spread of fire in a storage facility. High hazard materials require special precautions and safety measures to minimize the risk of fire and ensure the safety of the storage environment.

Submit
27. A Class I-A liquid has a boiling point __________degrees Fahrenheit.

Explanation

A Class I-A liquid has a boiling point below 100 degrees Fahrenheit.

Submit
28. In Group E occupancies, artwork on corridor walls shall be limited to ____% of the wall area.

Explanation

In Group E occupancies, the amount of artwork on corridor walls is limited to 20% of the wall area. This restriction is in place to ensure that the corridor remains clear and unobstructed for safe evacuation in case of an emergency. Limiting the amount of artwork helps to prevent clutter and allows for better visibility and movement within the corridor.

Submit
29. Exterior storage of finished lumber products requires a ___ foot high-security fence.

Explanation

The correct answer is 6. Exterior storage of finished lumber products requires a 6-foot high-security fence. This height is necessary to prevent unauthorized access and theft of the lumber products. A 6-foot fence provides a significant barrier and deterrent to potential intruders, ensuring the security of the stored lumber.

Submit
30. What is the minimum diameter of pipe, which can be used as part of a vehicle crash protection system?

Explanation

The minimum diameter of pipe that can be used as part of a vehicle crash protection system is 4. A larger diameter pipe would provide more strength and stability to absorb the impact of a crash, making it a more effective component for protection. A smaller diameter pipe may not be able to withstand the force of a crash and could potentially fail, compromising the safety of the vehicle occupants. Therefore, 4 is the minimum diameter required for adequate crash protection.

Submit
31. A Class I-A liquid has a boiling point __________degrees Fahrenheit.

Explanation

A Class I-A liquid has a boiling point below 100 degrees Fahrenheit. This means that the liquid will start to vaporize and turn into a gas at a temperature below 100 degrees Fahrenheit.

Submit
32. Which of the following editions of NFPA 13 is enforcible in the State of North Carolina?

Explanation

The correct answer is 2007 because in North Carolina, the edition of NFPA 13 that is enforceable is the 2007 edition. This means that any fire protection systems or installations must comply with the requirements and guidelines outlined in this specific edition.

Submit
33. Acme Print Shop has a two (2) remote, 36" exit doors. The building has a gross floor area of 6,000 square feet and is unsprinklered. Answer the following questions: What is the occupancy classification?

Explanation

The correct answer for this question is B. The occupancy classification of the building is B. This is because the building is a print shop, which falls under the Business occupancy classification according to the International Building Code (IBC). The fact that the building has two remote exit doors and a gross floor area of 6,000 square feet does not affect the occupancy classification in this case.

Submit
34. You are inspecting a tenant in a strip centre Business Occupancy. There are 2,100 square feet and the maximum travel distance is 70 feet from any point to an exit door in this light hazard occupancy. Occupancy is posted at 50. Answer the following 4 questions using this scenario. How many fire extinguishers will be needed?

Explanation

Based on the given information, the occupancy is a light hazard occupancy with a total area of 2,100 square feet. According to fire safety regulations, for light hazard occupancies, one fire extinguisher is required for every 3,000 square feet or fraction thereof. Since the area in this scenario is less than 3,000 square feet, only one fire extinguisher is needed. However, it is important to note that the fire extinguisher should be located properly to ensure easy access in case of a fire emergency.

Submit
35. Common areas of Residential Occupancies are required to be inspected ________.

Explanation

Residential occupancies are required to be inspected annually to ensure the safety and compliance of the building. This regular inspection helps identify any potential hazards, maintenance issues, or code violations that may pose a risk to the residents. By conducting these inspections annually, any necessary repairs or improvements can be made promptly, ensuring the well-being of the occupants and maintaining the overall integrity of the residential property.

Submit
36. Charcoal grills shall not be operated within ___ feet of combustible construction.

Explanation

Charcoal grills should not be operated within 10 feet of combustible construction. This is because charcoal grills produce heat and sparks that can potentially ignite flammable materials. Keeping a safe distance of 10 feet reduces the risk of fire and ensures the safety of the surrounding area.

Submit
37. The minimum stairway width of exit stairs in buildings with less than 50 occupants is _____ inches.

Explanation

The minimum stairway width of exit stairs in buildings with less than 50 occupants is 36 inches. This width is necessary to ensure that people can safely evacuate the building in case of an emergency. A wider stairway allows for easier movement and reduces the risk of overcrowding or tripping. It also provides enough space for individuals with mobility aids or disabilities to navigate the stairs comfortably. Therefore, 36 inches is the appropriate minimum width for exit stairs in smaller buildings.

Submit
38. Is storage permitted in an unoccupied covered mall tenant space?

Explanation

Storage is not permitted in an unoccupied covered mall tenant space.

Submit
39. How much gasoline, in an approved container, (for a leaf blower used to clean sidewalks), is allowed to be stored in this business?

Explanation

The correct answer is "Only that necessary for the operation of the leaf blower." This means that the business is only allowed to store the amount of gasoline that is required for the leaf blower to function properly. Any excess amount of gasoline beyond what is necessary is not allowed to be stored. This is likely a safety measure to prevent the risk of accidents or fires that could occur if there is an excessive amount of gasoline stored in the business.

Submit
40. Charcoal grills shall not be operated within ___ feet of combustible construction.

Explanation

Charcoal grills shall not be operated within 10 feet of combustible construction. This rule is in place to prevent the risk of fire. Charcoal grills produce open flames and intense heat, which can easily ignite combustible materials such as wood, paper, or plastic. By maintaining a distance of at least 10 feet, the risk of fire spreading to nearby structures or objects is significantly reduced. This safety measure helps to protect both property and individuals from potential harm.

Submit
41. What is the maximum distance from a gasoline dispenser to the emergency disconnect switch?

Explanation

The maximum distance from a gasoline dispenser to the emergency disconnect switch is 100. This means that the emergency disconnect switch should be located no more than 100 units of measurement (such as feet or meters) away from the gasoline dispenser. This distance is important to ensure that the switch can be easily accessed in case of an emergency or to quickly shut off the flow of gasoline if needed.

Submit
42. How often is a group R-4 Occupancy required to conduct fire drills?

Explanation

A group R-4 Occupancy is required to conduct fire drills quarterly, which means they should conduct fire drills every three months or four times a year. Additionally, the phrase "per shift" suggests that fire drills should be conducted for each shift within the occupancy, ensuring that all occupants are familiar with the emergency procedures and evacuation protocols.

Submit
43. What is the maximum term for a permit issued for a temporary tent location within a 12-month period on a single premise?

Explanation

A permit issued for a temporary tent location can be valid for a maximum term of 180 days within a 12-month period on a single premise. This means that the permit allows the temporary tent to be set up and used for up to 180 days before it needs to be removed or renewed. This timeframe allows for a reasonable amount of time for events or activities that require a temporary tent structure without being overly restrictive or permanent.

Submit
44. A high piled combustible storage warehouse is 12,000 square feet. The commodity is oil base paint in metal cans stored 20 feet high. The building has 4' draft curtains. There is NO sprinkler system. Answer the following 6 questions. How many curtained areas will this building have?

Explanation

The building will have 4 curtained areas because the total square footage of the warehouse is divided by the square footage of each curtained area. In this case, 12,000 square feet divided by the square footage of each curtained area will equal 4.

Submit
45. You are inspecting a tenant in a strip centre Business Occupancy. There are 2,100 square feet and the maximum travel distance is 70 feet from any point to an exit door in this light hazard occupancy. Occupancy is posted at 50. Answer the following 4 questions using this scenario. How many exit doors are required?

Explanation

Tables 1015.1 & 1021.1 P137 & 1021.1

Submit
46. LP-gas equipment shall be installed in accordance with __________.

Explanation

LP-gas equipment shall be installed in accordance with Both A & B, NFPA 58 and NFPA 59.

NFPA 58: This is the Liquefied Petroleum Gas Code, which provides criteria for the storage, handling, transportation, and use of LP-gas.

NFPA 59: This is the Utility LP-Gas Plant Code, which applies to the design, construction, location, installation, operation, and maintenance of refrigerated and non-refrigerated utility gas plants including LP-Gas containers, piping, and associated process equipment.

Please consult with a certified professional or the equipment manufacturer for the most accurate information. Also, always follow local regulations and codes, as they may have additional or different requirements.

Submit
47. An unobstructed fire break passageway or fire road not less than _____ feet wide and free from guy ropes shall be maintained on all sides of tents, canopies and membranes structures.

Explanation

An unobstructed fire break passageway or fire road not less than 12 feet wide and free from guy ropes shall be maintained on all sides of tents, canopies, and membrane structures. This is necessary to ensure that there is enough space for emergency personnel to access the structures in case of a fire. A wider passageway would be even better, but the minimum requirement is 12 feet.

Submit
48. Flammable liquids shall not be dispensed from tanks, drums, barrels or similar containers by _______ at garages.

Explanation

Flammable liquids should not be dispensed from tanks, drums, barrels, or similar containers by gravity at garages. This is because gravity flow can lead to uncontrolled and potentially dangerous spills or leaks. Using dippers, pressure, or siphon pumps allows for more controlled and regulated dispensing of flammable liquids, reducing the risk of accidents or fires.

Submit
49. In a Group A theatre, an announcement to notify occupants of exits to use, in the event of an emergency, shall be made ____ minutes prior to starting the program.

Explanation

In a Group A theatre, an announcement to notify occupants of exits to use, in the event of an emergency, shall be made 10 minutes prior to starting the program. This allows sufficient time for the occupants to familiarize themselves with the exit routes and be prepared in case of an emergency. Making the announcement 5 minutes prior may not provide enough time for everyone to react and evacuate safely, while making the announcement 15 or 20 minutes prior may cause unnecessary disruptions or delays. Therefore, 10 minutes is the most appropriate time for this announcement.

Submit
50. A fire watch shall be conducted for a minimum of _______ after the conclusion of any hot work involving welding and cutting.

Explanation

After the conclusion of any hot work involving welding and cutting, a fire watch should be conducted for a minimum of 30 minutes. This is necessary to ensure that any potential fire hazards or smoldering materials are identified and addressed promptly. It allows for sufficient time to monitor the area and ensure that all safety precautions are taken before considering the work completed. Conducting a fire watch for this duration helps to minimize the risk of fire incidents and ensures the safety of the surrounding environment and personnel.

Submit
51. Which ASTM Standard would apply to surface burning characteristics for building materials?

Explanation

ASTM E 84-07 is the correct answer because it specifically applies to surface burning characteristics for building materials. ASTM standards are widely recognized and used in various industries to ensure quality and safety. This particular standard provides a test method for determining the flame spread and smoke developed index of materials when exposed to a specific fire condition. It helps in evaluating the fire performance of building materials and aids in making informed decisions regarding their use in construction projects.

Submit
52. Unless by exception, exit signs in corridors shall be placed so there are no more than ____ feet to the nearest sign.

Explanation

Exit signs in corridors should be placed so that there are no more than 100 feet to the nearest sign. This is important for the safety of individuals in case of an emergency. Having exit signs placed within close proximity ensures that people can easily locate the nearest exit and evacuate the building quickly and efficiently. By keeping the distance between exit signs at a maximum of 100 feet, it reduces the chances of confusion or delay during an emergency situation.

Submit
53. The minimum width of exit stairs in buildings with less than 50 occupants is _____ inches.

Explanation

The minimum width of exit stairs in buildings with less than 50 occupants is 36 inches. This width is determined by building codes and regulations to ensure safe and efficient evacuation in case of emergencies. A wider stairway allows for easier movement of people and reduces the risk of congestion or tripping. It also provides enough space for emergency responders to access the building if needed. Therefore, a minimum width of 36 inches is necessary to meet safety standards and facilitate smooth evacuation.

Submit
54. What is the maximum distance from a gasoline dispenser to the emergency disconnect switch?

Explanation

The maximum distance from a gasoline dispenser to the emergency disconnect switch is 100. This means that the emergency disconnect switch should be within 100 units of distance from the gasoline dispenser. This is important for safety reasons, as having the switch within close proximity ensures that it can be easily accessed and used in case of an emergency or accident involving the gasoline dispenser.

Submit
55. According to the International Fire Code (IFC), what is the minimum required fire-resistance rating for fire walls separating buildings or subdividing a building to prevent the spread of fire?

Explanation



The International Fire Code (IFC) stipulates minimum standards for building safety to prevent fire hazards. A critical safety measure is the use of fire walls with sufficient fire-resistance ratings. Fire walls are required to have a minimum fire-resistance rating of 2 hours. This rating ensures a barrier against fire spread between compartments or adjacent buildings for up to two hours, providing crucial time for evacuation and firefighting efforts.
Submit
56. What is the minimum distance between a 660 gallon K-1 kerosene, Class II liquid protected above ground tank and any building at service stations?

Explanation

The minimum distance between a 660 gallon K-1 kerosene, Class II liquid protected above ground tank and any building at service stations is 5. This means that there should be at least a 5-foot distance between the tank and any building to ensure safety and compliance with regulations.

Submit
57. A restaurant, which seats 80 people, is classified as a(an) __________occupancy.

Explanation

The correct answer is A-2. A-2 occupancy refers to a restaurant that accommodates more than 50 people but less than 100 people. Since the restaurant in question can seat 80 people, it falls within the A-2 occupancy classification.

Submit
58. The guideline for installation of heating equipment is found in ____________, unless other codes or rules apply.

Explanation

The correct answer is "The manufacturer's instructions". When installing heating equipment, it is important to follow the guidelines provided by the manufacturer. These instructions are specific to the equipment being installed and will ensure proper installation and safe operation. While other codes or rules may apply in certain situations, the manufacturer's instructions should always be the primary source of guidance.

Submit
59. When converting these solid pounds to liquid gallons, the conversion rate would be 10 lb. of solid = _____ gallon(s) of liquids.

Explanation

When converting solid pounds to liquid gallons, the conversion rate is 10 lb. of solid = 1 gallon of liquid.

Submit
60. What is the maximum thickness of an interior trim material?

Explanation

The maximum thickness of an interior trim material is typically 3/4 inch. This thickness provides adequate structural support and allows for proper installation and finishing. Thicker trim materials can be more difficult to work with and may require specialized installation techniques.

Submit
61. An unobstructed fire break passageway or fire road not less than _____ feet wide shall be maintained on all sides of a tent or membrane structure.

Explanation

An unobstructed fire break passageway or fire road not less than 12 feet wide shall be maintained on all sides of a tent or membrane structure. This is necessary to ensure that there is enough space for emergency personnel and equipment to access the structure in the event of a fire. A wider passageway would be even better, but the minimum requirement is 12 feet.

Submit
62. If not complying with North Carolina Underground Storage Tank operating permit requirements, how long may underground combustible fuel tanks be out of service, before being removed or abandoned in place as per code?

Explanation

According to North Carolina Underground Storage Tank operating permit requirements, underground combustible fuel tanks can be out of service for up to 365 days before they need to be removed or abandoned in place. This means that the tanks can remain inactive for a year before action is required to either remove them or properly abandon them as per code.

Submit
63. Corridors shall be arranged so that there is no dead end in excess of ___ feet.

Explanation

Corridors should be designed in a way that there are no dead ends exceeding 20 feet. This is important for safety and to ensure easy access and evacuation in case of emergencies. Dead ends can impede movement and increase the risk of accidents or delays in exiting the building. By limiting the length of dead ends to 20 feet, the design promotes efficient circulation and enhances the overall safety of the building.

Submit
64. A Type ____ hood is a kitchen hood for collecting and removing grease vapours and smoke.

Explanation

A Type I hood is a kitchen hood specifically designed for collecting and removing grease vapours and smoke. Type I hoods are commonly used in commercial kitchens where there is a high volume of cooking and a greater need for ventilation and grease removal. These hoods are equipped with grease filters and are designed to handle the heat and grease produced during cooking processes.

Submit
65. A Class ____ interior finish material has a flame spread index of 26-75 and a smoke developed index of 0-450.

Explanation

Class B interior finish material has a flame spread index of 26-75 and a smoke developed index of 0-450. This means that it has a moderate flame spread and can withstand moderate exposure to fire. It also produces a moderate amount of smoke when exposed to fire.

Submit
66. High Piled Combustible Storage is generally defined as combustible storage of materials in closely packed piles or combustible materials on pallets, racks or on shelves where the top of the storage is greater than _____ feet in height.

Explanation

High Piled Combustible Storage is defined as combustible storage of materials in closely packed piles or on pallets, racks, or shelves where the top of the storage is greater than 12 feet in height. This means that if the storage exceeds 12 feet in height, it is considered high piled combustible storage.

Submit
67. A recreational fire shall be ____ feet from any structure or combustible material.

Explanation

A recreational fire should be 25 feet away from any structure or combustible material to ensure safety. This distance helps to prevent the fire from spreading and causing damage to nearby buildings or objects that can easily catch fire. By maintaining this distance, the risk of accidents or injuries is minimized, allowing people to enjoy their recreational fire in a controlled and safe manner.

Submit
68. Acme Print Shop has a two (2) remote, 36" exit doors. The building has a gross floor area of 6,000 square feet and is unsprinklered. Answer the following questions: If this building had an egress stair, how much egress width per person is required?

Explanation

The correct answer is .3. In order to determine the egress width per person required, we need to calculate the total number of occupants in the building. According to the International Building Code (IBC), the egress width per person is determined by dividing the total occupant load by the egress width factor. For unsprinklered buildings, the egress width factor is 0.3. Since the question does not provide the occupant load, we cannot calculate the exact egress width per person. However, we can conclude that the correct answer is .3 based on the given egress width factor for unsprinklered buildings.

Submit
69. Installation of a flammable liquid spray booth requires a/an _______ permit.

Explanation

The correct answer is "required" because the installation of a flammable liquid spray booth involves potential fire hazards. To ensure safety and compliance with regulations, a permit is necessary to ensure that the installation meets specific standards and guidelines. Without a permit, the installation may be deemed unsafe and not up to code, which could pose a risk to the environment and individuals working in the area.

Submit
70. Gas meters shall be protected with barriers complying with Section _____ of IFC.

Explanation

Gas meters shall be protected with barriers complying with Section 312 of the International Fire Code (IFC). This section specifically addresses the protection of gas meters and outlines the requirements for barriers to prevent damage or tampering. By implementing these barriers, the risk of accidents or unauthorized access to the gas meters can be minimized, ensuring the safety and functionality of the gas system.

Submit
71. What is the minimum distance between a 660 gallon K-1 kerosene, Class II liquid protected above-ground tank and any building at service stations?

Explanation

According to the International Fire Code (IFC), the minimum distance between a 660-gallon K-1 kerosene, Class II liquid protected above-ground tank and any building at service stations is 25 feet. This separation distance is crucial for fire safety, preventing the spread of fire from the tank to the building or vice versa.

Submit
72. A portable fire extinguisher shall be located within ___ feet of commercial cooking equipment.

Explanation

A portable fire extinguisher should be located within 30 feet of commercial cooking equipment. This is important because in the event of a fire, quick access to a fire extinguisher is crucial to suppress or control the fire before it spreads. Placing the extinguisher within 30 feet ensures that it is within reach and can be used effectively in case of an emergency.

Submit
73. Fire apparatus access roads shall have an unobstructed width of not less than _______ feet.

Explanation

not-available-via-ai

Submit
74. Ceiling clearance from combustible materials shall be maintained at _____ below the ceiling in non-sprinklered buildings.

Explanation

In non-sprinklered buildings, the ceiling clearance from combustible materials should be maintained at 24 inches below the ceiling. This clearance is necessary to prevent the risk of fire spreading to the ceiling and causing significant damage. By maintaining this distance, there is a reduced chance of ignition and the potential for a fire to grow and spread rapidly. This requirement helps to ensure the safety of occupants and minimize the potential for property damage in non-sprinklered buildings.

Submit
75. The minimum width of a means of egress in a tent is__________ inches.

Explanation

The minimum width of a means of egress in a tent is 72 inches. This is because a means of egress is a pathway that allows people to safely exit a building or structure in case of an emergency. In the case of a tent, a wider width ensures that people can easily and quickly evacuate the area without any obstructions or difficulties. A wider means of egress also allows for better crowd flow and reduces the risk of congestion or trampling during an emergency situation.

Submit
76. You are inspecting a tenant in a strip centre Business Occupancy. There are 2,100 square feet and the maximum travel distance is 70 feet from any point to an exit door in this light hazard occupancy. Occupancy is posted at 50. Answer the following 4 questions using this scenario. What is the minimum fire extinguisher rating?

Explanation

Based on the scenario provided, the minimum fire extinguisher rating required would be 2-A: 10-B: C. This rating is determined based on the size of the occupancy and the maximum travel distance to an exit door. In this case, the occupancy is 2,100 square feet and the maximum travel distance is 70 feet. The rating of 2-A indicates that the fire extinguisher can effectively combat fires involving ordinary combustible materials, such as wood or paper. The rating of 10-B indicates that it can also handle fires involving flammable liquids, such as gasoline or oil. The C rating indicates that it can be used on fires involving electrical equipment. Therefore, a 2-A: 10-B: C rated fire extinguisher would be the minimum requirement for this scenario.

Submit
77. When dispenser nozzles are stretched out, they shall not be within ___ of any building opening.

Explanation

When dispenser nozzles are stretched out, they shall not be within 5 feet of any building opening. This is because having the dispenser nozzles too close to a building opening can pose a fire hazard. Keeping a safe distance of at least 5 feet helps to prevent any potential ignition sources from reaching the building opening and causing a fire.

Submit
78. Aisles in high piled storage facilities, which have no sprinkler system, shall be _____inches in width.

Explanation

Aisles in high piled storage facilities that do not have a sprinkler system need to be 96 inches in width. This is because wider aisles provide more space for maneuvering and allow for better access in case of emergencies. In the absence of a sprinkler system, it is important to have wider aisles to ensure the safety of personnel and to facilitate the movement of equipment and materials.

Submit
79. A big box retail hardware store is going to sell swimming pool chlorine (Class II Oxidizer) in solid form. The building of a one-story building has an approved sprinkler system. Storage is on pallets in 5-pound buckets on the floor. Answer the following 5 questions using this scenario. [Mercantile] How high can the containers be stacked?

Explanation

In this scenario, the correct answer is 6 feet. This is because the building has an approved sprinkler system, which means it is equipped to handle potential fire hazards. Stacking the containers up to 6 feet allows for efficient use of space while still maintaining a safe distance from the floor. Stacking them higher may increase the risk of accidents or make it more difficult for the sprinkler system to effectively reach all areas in case of a fire.

Submit
80. A big box retail hardware store is going to sell swimming pool chlorine (Class II Oxidizer) in solid form. The building of a one-storey building has an approved sprinkler system. Storage is on pallets in 5-pound buckets on the floor. Answer the following 5 questions using this scenario. [Mercantile] How many separate control areas are allowed?

Explanation

In this scenario, the building is a one-storey building with an approved sprinkler system. The swimming pool chlorine, which is a Class II Oxidizer, is stored on pallets in 5-pound buckets on the floor. According to the National Fire Protection Association (NFPA) guidelines for mercantile occupancies, the number of separate control areas allowed is determined by the hazard classification of the materials stored. Since the chlorine is classified as a Class II Oxidizer, which is a higher hazard class, the guidelines allow for a maximum of 4 separate control areas. Therefore, the correct answer is 4.

Submit
81. A high piled combustible storage warehouse is 12,000 square feet. The commodity is oil base paint in metal cans stored 20 feet high. The building has 4' draft curtains. There is NO sprinkler system. Answer the following 6 questions. What is the commodity Class?

Explanation

The commodity class for the given scenario is Class III. This is because oil-based paint in metal cans falls under Class III combustible liquids as per the National Fire Protection Association (NFPA) classification system. Class III liquids have a flash point at or above 100 degrees Fahrenheit and below 140 degrees Fahrenheit. They pose a moderate fire hazard and can ignite under certain conditions.

Submit
82. The Screens upon which motion pictures are projected shall either be flame resistant as demonstrated by complying with NFPA 703 or shall comply with the requirements for a Class ________ interior finish.

Explanation

The correct answer is B. The screens upon which motion pictures are projected should comply with the requirements for a Class B interior finish. This means that the screens should have a certain level of fire resistance to ensure safety in case of a fire. NFPA 703 is a standard that determines the flame resistance of materials, and complying with it is one way to meet the requirements for a Class B interior finish.

Submit
83. A working clearance of ________ inches in width shall be provided in front of electrical service equipment.

Explanation

A working clearance of 30 inches in width should be provided in front of electrical service equipment. This clearance is necessary to ensure that there is enough space for maintenance and repair work to be conducted safely. It allows electricians to access the equipment and work on it without any obstructions or hazards. Providing this clearance helps prevent accidents and ensures that electrical service equipment can be operated and maintained effectively.

Submit
84. Acme Print Shop has a two (2) remote, 36" exit doors. The building has a gross floor area of 6,000 square feet and is unsprinklered. Answer the following questions: What is the required gross floor area per occupant in square feet?

Explanation

not-available-via-ai

Submit
85. Which of the following is NOT a primary duty of a Fire Inspector?

Explanation

While Fire Inspectors play a crucial role in fire safety, their primary focus is on prevention and code enforcement. They inspect buildings and facilities to identify potential hazards, ensure compliance with fire safety regulations, and recommend corrective measures. They also investigate the causes of fires to understand how to prevent similar incidents in the future. Educating the public about fire safety is another key aspect of their job. The actual task of extinguishing fires and rescuing occupants falls under the responsibility of firefighters.

Submit
86. In a lumber production facility, portable fire extinguishers shall be placed so that travel distance to machinery producing wood shavings doesn't exceed ____ feet.

Explanation

In a lumber production facility, portable fire extinguishers need to be placed within a certain distance from machinery producing wood shavings to ensure quick access in case of a fire. The correct answer is 50 feet, as this distance allows for efficient and timely response to potential fire hazards. Placing the fire extinguishers too far away could result in delays in extinguishing the fire, potentially leading to more damage and danger. Conversely, placing the fire extinguishers too close to the machinery could put them at risk of being damaged or rendered inaccessible during an emergency situation.

Submit
87. At what amount does the storage, use or handling (at normal temperature and pressure) of Corrosive gases require an operational permit?

Explanation

The storage, use, or handling of corrosive gases requires an operational permit when the amount exceeds 200 cubic feet. This means that if the amount of corrosive gases is equal to or less than 200 cubic feet, an operational permit is not required.

Submit
88. A high piled combustible storage warehouse is 12,000 square feet. The commodity is oil base paint in metal cans stored 20 feet high. The building has 4' draft curtains. There is NO sprinkler system. Answer the following 6 questions. What is the size of the vent opening (in square feet) in each curtained area?

Explanation

The size of the vent opening in each curtained area is 40 square feet.

Submit
89. A high piled combustible storage warehouse is 12,000 square feet. The commodity is oil base paint in metal cans stored 20 feet high. The building has 4' draft curtains. There is NO sprinkler system. Answer the following 6 questions. What is the maximum spacing of vents on centre, in curtain areas?

Explanation

The maximum spacing of vents on center in curtain areas is 100 feet. This is important because in a high piled combustible storage warehouse, proper ventilation is crucial to prevent the buildup of flammable gases and reduce the risk of fire. With a spacing of 100 feet, the vents are strategically placed to allow for adequate airflow and ventilation throughout the warehouse, helping to maintain a safe environment.

Submit
90. A high piled combustible storage warehouse is 12,000 square feet. The commodity is oil base paint in metal cans stored 20 feet high. The building has 4' draft curtains. There is NO sprinkler system. Answer the following 6 questions. What is the capacity of each vent fan?

Explanation

The capacity of each vent fan is 12,000 cfm.

Submit
91. The area within ____ feet of an above-ground flammable liquid tank vent, shall be classified as a Class 1, Group D, Division 1, Electrical Equipment Location.

Explanation

The area within 3 feet of an above-ground flammable liquid tank vent is classified as a Class 1, Group D, Division 1, Electrical Equipment Location. This classification is necessary because the proximity to the vent increases the risk of flammable vapors being present, which requires electrical equipment to be specifically designed and installed to prevent ignition of these vapors.

Submit
92. A big box retail hardware store is going to sell swimming pool chlorine (Class II Oxidizer) in solid form. The building of a one storey building has an approved sprinkler system. Storage is on pallets in 5-pound buckets on the floor. Answer the following 5 questions using this scenario. [Mercantile] What is the maximum allowable quantity per control area?

Explanation

The maximum allowable quantity per control area for the solid form of swimming pool chlorine (Class II Oxidizer) in a one-story building with an approved sprinkler system and storage on pallets in 5-pound buckets on the floor is 4500 lbs. This means that the retail hardware store can store up to 4500 lbs of swimming pool chlorine in the building without exceeding the safety limits.

Submit
93. A high piled combustible storage warehouse is 12,000 square feet. The commodity is oil base paint in metal cans stored 20 feet high. The building has 4' draft curtains. There is NO sprinkler system. Answer the following 6 questions. Access is required to within _____ feet of all exterior walls of this building.

Explanation

According to the International Fire Code (IFC) and NFPA 1 (Uniform Fire Code), for buildings with high-piled combustible storage, access roads should be provided within 150 feet of all exterior walls to allow for fire department operations. This requirement helps ensure that fire service personnel can effectively reach and combat any fires that may occur within such facilities. While specific codes and editions might vary slightly in their requirements, the 150-foot access provision is a common standard aimed at enhancing fire safety for high-piled storage areas.

Submit
94. In Plywood, Veneer and Composite Board Mills, manual deluge activation valves shall be located withing ______ feet of drying equipment.

Explanation

In Plywood, Veneer and Composite Board Mills, manual deluge activation valves need to be located within 75 feet of drying equipment. This is important because in case of a fire or emergency, the deluge system needs to be activated quickly to minimize damage and ensure the safety of personnel. Having the valves within close proximity to the drying equipment allows for a faster response time and quicker activation of the deluge system.

Submit
95. A big box retail hardware store is going to sell swimming pool chlorine (Class II Oxidizer) in solid form. The building of a one-storey building has an approved sprinkler system. Storage is on pallets in 5-pound buckets on the floor. Answer the following 5 questions using this scenario. [Mercantile] What is the required width of aisles in feet?

Explanation

The required width of aisles in feet is 4. This is determined by the occupancy classification of the building, which in this case is mercantile. According to the International Building Code (IBC), mercantile buildings with an approved sprinkler system are required to have a minimum aisle width of 4 feet. This allows for safe and easy movement of people and equipment throughout the space, ensuring proper access to the swimming pool chlorine and other materials stored on pallets in 5-pound buckets on the floor.

Submit
96. In Group I-1 Occupancies, staff training procedures, are to be reviewed every ________months.

Explanation

In Group I-1 Occupancies, staff training procedures are required to be reviewed every 2 months. This regular review ensures that staff members are kept up to date with any changes or updates in procedures, ensuring the safety and well-being of the occupants in these types of facilities. By reviewing the training procedures every 2 months, any necessary updates or adjustments can be made in a timely manner, maintaining the highest level of safety standards.

Submit
97. Acme Print Shop has a two (2) remote, 36" exit doors. The building has a gross floor area of 6,000 square feet and is unsprinklered. Answer the following questions: What is the maximum travel distance to an exit?

Explanation

Based on the given information, the maximum travel distance to an exit in Acme Print Shop is 200 feet. This is determined by the fact that the building is unsprinklered and has a gross floor area of 6,000 square feet. According to fire safety regulations, buildings without sprinklers typically have a maximum travel distance of 200 feet to ensure that occupants can safely reach an exit in case of an emergency.

Submit
98. The required interior finish on room walls in an unsprinklered Educational Occupancy is Class ____.

Explanation

In an unsprinklered Educational Occupancy, the required interior finish on room walls is Class C. This means that the walls should have materials that have a low flame spread and smoke development rating. Class C materials are considered to have moderate fire resistance, making them suitable for educational buildings where fire safety is important.

Submit
99. Outdoor storage of portable tanks of Class IB flammable liquids totalling 1,000 gallons must be ____ feet or more from the nearest lot line that can be built upon.

Explanation

The outdoor storage of portable tanks containing Class IB flammable liquids totaling 1,000 gallons must be at least 25 feet away from the nearest lot line that can be built upon. This distance is necessary to ensure the safety of nearby structures and minimize the risk of fire spreading in case of an accident or leakage.

Submit
100. Class ___ liquids storage shall be allowed to be stored in basements provided that automatic suppression and other fire protection are provided in accordance with Chapter 9.

Explanation

Class I, II, and IIIA liquids are all flammable or combustible liquids. Storing these liquids in basements requires additional fire protection measures, such as automatic sprinkler systems and adequate ventilation, to mitigate the risk of fire and ensure the safety of occupants and property.

Submit
View My Results

Quiz Review Timeline (Updated): Jan 21, 2025 +

Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.

  • Current Version
  • Jan 21, 2025
    Quiz Edited by
    ProProfs Editorial Team
  • Jan 09, 2013
    Quiz Created by
    NCFMA
Cancel
  • All
    All (100)
  • Unanswered
    Unanswered ()
  • Answered
    Answered ()
The ____________, upon finding any overcrowding conditions above the...
Exits shall discharge directly to ___________ of the building.
Portable electric heaters, of all types, are __________ in any...
Commercial cooking equipment using animal or vegetable oils shall be...
Unvented, portable fuel-fired heating equipment is prohibited in ___...
Where _______, unattended self-service station is permitted.
An outdoor fire, for ceremonial purpose having a fuel diameter area of...
A device, which has the appearance of life safety or fire protection...
Horizontal and vertical sliding and rolling fire doors shall be...
An enclosed or separated space within a building, where hazardous...
Horizontal sliding fire doors shall be tested _______ to confirm...
The required turning radius of a fire apparatus road shall be...
When fire door hold open devices in Fire-Resistant-Rated buildings,...
Required fire walls, fire barriers, and fire...
How many chock blocks are required on a gasoline transport tanker?
When is a repair garage required to have a sprinkler system?
The ____________ or the fire department official in charge of an...
Class III standpipe systems shall be installed when the lowest floor...
Which of the following structures is/are exempt from the requirements...
Fuel dispensing devices shall be _____________ the attendant at all...
Class III standpipe systems shall be installed when the lowest floor...
Fire safety and evacuation plans shall be reviewed or updated...
A code official may extend any permit for a period not to exceed...
The fire code requirement, for Liquefied Petroleum Gases (LPG) tank...
Exterior lumber piles shall not exceed ____ feet in height.
What commodity class, for high piled combustible storage, are foam...
A Class I-A liquid has a boiling point __________degrees Fahrenheit.
In Group E occupancies, artwork on corridor walls shall be limited to...
Exterior storage of finished lumber products requires a ___ foot...
What is the minimum diameter of pipe, which can be used as part of a...
A Class I-A liquid has a boiling point __________degrees Fahrenheit.
Which of the following editions of NFPA 13 is enforcible in the State...
Acme Print Shop has a two (2) remote, 36" exit doors. The building has...
You are inspecting a tenant in a strip centre Business Occupancy....
Common areas of Residential Occupancies are required to be inspected...
Charcoal grills shall not be operated within ___ feet of combustible...
The minimum stairway width of exit stairs in buildings with less than...
Is storage permitted in an unoccupied covered mall tenant space?
How much gasoline, in an approved container, (for a leaf blower used...
Charcoal grills shall not be operated within ___ feet of combustible...
What is the maximum distance from a gasoline dispenser to the...
How often is a group R-4 Occupancy required to conduct fire drills?
What is the maximum term for a permit issued for a temporary tent...
A high piled combustible storage warehouse is 12,000 square feet. The...
You are inspecting a tenant in a strip centre Business Occupancy....
LP-gas equipment shall be installed in accordance with __________.
An unobstructed fire break passageway or fire road not less than _____...
Flammable liquids shall not be dispensed from tanks, drums, barrels or...
In a Group A theatre, an announcement to notify occupants of exits to...
A fire watch shall be conducted for a minimum of _______ after the...
Which ASTM Standard would apply to surface burning characteristics for...
Unless by exception, exit signs in corridors shall be placed so there...
The minimum width of exit stairs in buildings with less than 50...
What is the maximum distance from a gasoline dispenser to the...
According to the International Fire Code (IFC), what is the minimum...
What is the minimum distance between a 660 gallon K-1 kerosene, Class...
A restaurant, which seats 80 people, is classified as a(an)...
The guideline for installation of heating equipment is found in...
When converting these solid pounds to liquid gallons, the conversion...
What is the maximum thickness of an interior trim material?
An unobstructed fire break passageway or fire road not less than _____...
If not complying with North Carolina Underground Storage Tank...
Corridors shall be arranged so that there is no dead end in excess of...
A Type ____ hood is a kitchen hood for collecting and removing grease...
A Class ____ interior finish material has a flame spread index of...
High Piled Combustible Storage is generally defined as combustible...
A recreational fire shall be ____ feet from any structure or...
Acme Print Shop has a two (2) remote, 36" exit doors. The building has...
Installation of a flammable liquid spray booth requires a/an _______...
Gas meters shall be protected with barriers complying with Section...
What is the minimum distance between a 660 gallon K-1 kerosene, Class...
A portable fire extinguisher shall be located within ___ feet of...
Fire apparatus access roads shall have an unobstructed width of not...
Ceiling clearance from combustible materials shall be maintained at...
The minimum width of a means of egress in a tent is__________ inches.
You are inspecting a tenant in a strip centre Business Occupancy....
When dispenser nozzles are stretched out, they shall not be within ___...
Aisles in high piled storage facilities, which have no sprinkler...
A big box retail hardware store is going to sell swimming pool...
A big box retail hardware store is going to sell swimming pool...
A high piled combustible storage warehouse is 12,000 square feet. The...
The Screens upon which motion pictures are projected shall either be...
A working clearance of ________ inches in width shall be provided in...
Acme Print Shop has a two (2) remote, 36" exit doors. The building has...
Which of the following is NOT a primary duty of a Fire Inspector?
In a lumber production facility, portable fire extinguishers shall be...
At what amount does the storage, use or handling (at normal...
A high piled combustible storage warehouse is 12,000 square feet. The...
A high piled combustible storage warehouse is 12,000 square feet. The...
A high piled combustible storage warehouse is 12,000 square feet. The...
The area within ____ feet of an above-ground flammable liquid tank...
A big box retail hardware store is going to sell swimming pool...
A high piled combustible storage warehouse is 12,000 square feet. The...
In Plywood, Veneer and Composite Board Mills, manual deluge activation...
A big box retail hardware store is going to sell swimming pool...
In Group I-1 Occupancies, staff training procedures, are to be...
Acme Print Shop has a two (2) remote, 36" exit doors. The building has...
The required interior finish on room walls in an unsprinklered...
Outdoor storage of portable tanks of Class IB flammable liquids...
Class ___ liquids storage shall be allowed to be stored in basements...