Industrial refrigerant machine operators seem to be simple people within the production chain but essentially are very important. Take up the quiz below and see how good you are as a refrigerant machine operator. All the best.
7.7
0.6
5.9
23.5
HEAD PSI DROPPING TO LOW
DECREASE THE CAPACITY OF THE COMPRESSOR AND REFRIGERATION SYSTEM
NON-CONDENSABLES ARE MORE PRONE TO COLLECT IN THE SYSTEM
FROST MAY DEVELOP IN THE SUCTION LINE
Rate this question:
INDIRECT SYSTEMS
DIRECT SYSTEMS
INDIRECT CLOSED SYSTEMS
INDRIECT OPEN SYSTEMS
Rate this question:
FILTER SUCTION AND DISCHARGE VALVES
SUCTION VALVE AND DISCHARGE BYPASS BOTH OPEN
SUCTION BYPASS AND DISCHARGE VALVE BOTH OPEN
DISCHARGE BYPASS AND SUCTION VALVE BOTH CLOSED
Rate this question:
DECREASE IN SUPER HEAT TEMP ENTERING COMPRESSOR
AN INCREASE IN COMPRESSOR HEAD PRESSURE
AN INCREASE IN THE FLOW RATE OF NONCONDENSABLES
CONDENSER TO METERING DEVICE FROZEN
Rate this question:
NOT ENOUGH REFRIGERANT IN SYSTEM
EXPANSION VALVE OPEN TOO WIDE
THE COMPRESSOR IS RUNNING CONTINUALLY
COMPRESSOR VALVES ARE LEAKING
Rate this question:
80°F
90°F
110°F
130°F
Rate this question:
A1
B2
A3
B1
Rate this question:
HIGH PRESSURE GAS AND LEAVES AS LOW PRESSURE LIQUID
HIGH PRESSURE GAS AND LEAVES AS HIGH PRESSURE LIQUID
SUPERHEATED GAS AND LEAVES AS HIGH TEMPERATURE LIQUID
HIGH TEMPERATURE GAS AND LEAVES AS SUPERHEATED GAS
Rate this question:
GROUP 1
GROUP 2
GROUP 3
GROUP 4
Rate this question:
REDUCE BY 1/2
INCREASE BY A FACTOR OF 2
STAY THE SAME
INCREASE BY A FACTOR OF 4
Rate this question:
WATER, OIL, REFRIGERANT
OIL, REFRIGERANT, WATER
REFRIGERANT, OIL, WATER
OIL, WATER, REFRIGERANT
Rate this question:
1204
1002
1808
1406
Rate this question:
32
28
40
18
Rate this question:
DOUBLE INDIRECT OPEN SPACE SYSTEMS
SYSTEMS OPERATING BELOW ATMOSPHERIC PRESSURE
ABSORPTION COMPRESSORS
OUTSIDE AIR DAMPERS
Rate this question:
VAPOR RECYCLING UNIT
AN ECONOMIZER
REFRIGERANT CLEANER
EVAPORATOR
Rate this question:
CONDENSER
ECONOMIZER
COMPRESSOR DISCHARGE
EVAPORATOR
Rate this question:
REDUCING PRESSURE
RAISING PRESSURE
REGULATING PRESSURE
STABILIZING PRESSURE
Rate this question:
A REDUCTION ON BOTH THE WATER FLOW RATE AND PRESSURE INTO THE CONDENSER
A REDUCTION IN TOTAL FLOW RATE TO CONDENSER
A REDUCTION IN WATER PRESSURE AT THE CONDENSER INLET
FOR THE PUMPS TO COMPENSATE TO MAINTAIN BOTH THE FLOW RATE AND DISCHARGE PRESSURE
Rate this question:
1.2 OF DESIGN PRESSURE (AT LEAST)
THE RUPTURE GUARD HAS TO BE REPLACED ALSO
THE GAUGE HAS TO BE A COMPOUND GAUGE
THE GAUGE SHOULD BE GRADUATED TO PRESSURE
Rate this question:
INSPECTION SHOULD BE MADE FOR DIRTY TEV STRAINER
PARTIALLY CLOGGED DISCHARGE LINE
CHECK COMPRESSOR WIRING, FOR OVERLOADED EQUIPMENT
ADDITIONAL REFRIGERANT BE CHARGED
Rate this question:
PRESSURE FITTING
GAS TIGHT FITTING
START TO MELT AT 400°F
START TO MELT AT 500°F
Rate this question:
RE-ADJUST THE TEV SUPERHEAT SETTING
DEACTIVATE THE FREEZE STAT
RAISE THE COMPRESSOR DISCHARGE OPERATING PRESSURE
LOWER THE COMPRESSOR SUCTION OPERATING PRESSURE
Rate this question:
LOW CORRESPONDING COMPRESSOR DISCHARGE TEMP
LOW VISCOSITY
LOW LATENT HEAT
LOW CORRESPONDING OPERATING PRESSURE
Rate this question:
SCALE PARTICLES LODGED IN THE TEV VALVE
UNRAVELING OF THE INSULATION PROTECTING THE TEV VALVE THERMAL BULB
BUILD-UP OF NONCONDENSABLES IN THE CONDENSER
OVERCHARGE OF REFRIGERANT
Rate this question:
FAULTY MACHINE CONTROL
PROPER REFRIGERATION CHARGE
FAULTY COMPRESSOR VALVES
POOR CONDENSER OPERATION / DIRTY TUBES
Rate this question:
MUST ENSURE THE FLAME IS ENCLOSED AND VENTED TO OPEN AIR
MAY MAKE REPAIRS AT LEAST 25 FEET FROM THE REFRIGERANT UNIT
MAY MAKE REPAIRS WITHOUT ANY RESTRICTIONS IF THE REFRIGERATING UNIT IS SHUT DOWN
MAY NOT MAKE REPAIR UNDER ANY CIRCUMSTANCES
Rate this question:
SOLENOID VALVE
HIGH SIDE FLOAT
THERMAL EXPANSION VALVE
CAPILLARY TUBE
Rate this question:
OPENING THE SUCTION VALVES WITH SOME FORM OF CONTROL
CONTROLLING THE DISCHARGE PRESSURE
CHANGING THE STROKE AND ADDING RE-EXPANSION VOLUME
RETURNING THE DISCHARGE GAS TO SUCTION
Rate this question:
HIGH COOLING WATER BEING RETURNED
RISE IN CONDENSER HEAD PRESSURE
LOWER COOLING WATER TEMPERATURE RETURN
NO NOTICEABLE EFFECT OF THE COOLING TOWER TEMP BEING RETURNED
Rate this question:
5% OVER DESIGN PRESSURE
THE DESIGN PRESSURE
RECOMMENDED OPERATING PRESSURE FOR NORMAL COOLING CONDITIONS
20% BELOW DESIGN PRESSURE
Rate this question:
HIGH PRESSURE SIDE OF THE EQUIPMENT
LOW PRESSURE SIDE OF THE EQUIPMENT
DISCHARGE SIDE OF THE EQUIPMENT
RECIEVER
Rate this question:
PURGE AT RAPID RATE
PURGE WITH COMPRESSOR ON
STOP WHEN PRESSURE CEASES TO DROP
RUN THE CONDENSER AS MUCH AS POSSIBLE
Rate this question:
AS HEAT OF EVAPORATION OF THE COOLING TOWER
IN THE ECONOMIZER
IN THE EVAPORATOR
CONDENSER WATER OUTLET
Rate this question:
R-22
CALCIUM CHLORIDE
GLOCOL
SODIUM CHLORIDE
Rate this question:
WATTS = VOLTS X AMPS X OHMS
WATTS = VOLTS X AMPS X HERTZ
WATTS = VOLTS X AMPS
WATTS = VOLTS X AMPS X POWER FACTOR
Rate this question:
R-22
R-12
CARBON DIOXIDE
BUTANE
Rate this question:
TWO WAY VALVE
THREE WAY VALVE
PLUG VALVE
STOP VALVE
Rate this question:
ALL THE CYLINDERS
THE CLEARANCE SPACES IN THE CYLINDERS
CONTROL CAPACITY BY SHUTTING DOWN THE COMPRESSOR
CYLINDERS THAT CAN BE UNLOADED
Rate this question:
RAISE THE CONDENSER LIQUID LEVEL TO THE MAXIMUM
PRODUCE A LARGE AMOUNT OF LIQUID SUB-COOLING
RAISE THE CONDENSER HEAD PRESSURE
LOWER THE CONDENSER PRESSURE
Rate this question:
AT HIGHER EVAPORATIVE TEMPERATURE AND LOW CONDENSER TEMPERATURE
LOW EVAPORATIVE TEMPERATURE AND HIGH CONDENSER TEMPERATURE
HIGHER EVAPORATIVE TEMPERATURE AND HIGH CONDENSER TEMPERATURE
LOW EVAPORATIVE TEMPERATURE AND LOW CONDENSER TEMPERATURE
Rate this question:
BALL
PLUG
GLOBE
GATE
Rate this question:
SEWER IS NOT CONNECTED TO A STORM DRAIN
FIRST CONFIRM THAT REFRIGERANT IS NOT FLAMMABLE
FACILITY MANAGER APPROVES IT
YOU DISCHARGE UNDER THE SUPERVISION OF THE FIRE DEPT.
Rate this question:
CLOSE, THE COMPRESSOR PUMPS DOWN AND SHUTS DOWN ON LOW PRESSURE
CLOSE AND THE COMPRESSOR WILL START ON HIGH PRESSURE
OPEN AND COMPRESSOR WILL PUMP DOWN AND GO OFF ON HIGH PRESSURE
OPEN AND COMPRESSOR WILL CONTINUE TO RUN AT REDUCED SPEED
Rate this question:
THE FLOW OF OIL WILL NOT BE EFFECTED
YOU WILL HAVE INSUFFICIENT HEAD TO LIFT THE OIL
THE TEMPERATURE OF THE REFRIGERANT EXITING THE JETS WILL DECREASE
THE OIL IN THE BOTTOM OF THE CHILLER WILL NOT LIFT IF IT BECOMES MIXED WITH LESS REFRIGERANT
Rate this question:
LIQUID LEVEL IN CONDENSER WILL FALL TOO LOW
COMPRESSOR WILL WORK HARDER
EXPANSION VALVES WILL NOT FEED PROPERLY
HEAD PRESSURE WILL INCREASE
Rate this question:
INCREASE WITH THE VELOCITY OF THE WATER IN THE TUBES
SHOW ONLY A SMALL INCREASE IF TUBES ARE DESCALED
INCREASE WITH A LOWER LEAVING WATER TEMPERATURE DIFFERENCE
SHOW THE LEAST BENEFIT FOR DESCALING THE TUBES AT HIGH WATER VELOCITIES
Rate this question:
YOU COULD BREAK THE RUPTURE GUARD WITH LIQUID
YOU CAN ENTRAIN THE OIL IN THE REFRIGERANT WITH LIQUID
YOU CAN FREEZE WATER IN THE TUBES WITH LIQUID
YOU CAN OVER CHARGE THE SYSTEM WITH LIQUID
Rate this question:
Quiz Review Timeline (Updated): Apr 16, 2024 +
Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.
Wait!
Here's an interesting quiz for you.