Test Technician Level 2 Test 3. Test consists of 50 Questions. Test has 90 minute time limit. You may use a calculator and look up any formulas not given. Allow yourself at least an hour to complete as you cannot save and resume the test later. Good Luck!
47
59
86
27
67
Rate this question:
The 2 point method
The fall of potential method
The 3 point method
The use of 4 electrodes
Rate this question:
500 MCM copper cable
350 MCM aluminum cable
1/4 x 6 aluminum bus
1/4 x 6 copper bus
1/2 x 2 copper bus
Rate this question:
Stored energy operated
Motor operated
Closing coil operated
Non load-break
Hook stick operated
Rate this question:
An instantaneous overcurrent relay
Phase balance relaying
Arrestors
Current limiting fuses
Equipment maximum voltage ratings
Rate this question:
Worker safety
Dust and dirt control
Moisture control
Fault damage control
All of the above
Rate this question:
On radial feeders
To prevent the motoring of a generator
To protect buses
On double ended substations with closed bus ties
B and C
Rate this question:
13,200
13,860
13,530
12,870
12,540
Rate this question:
Hysteresis
Saturation
Corona
Eddy currents
None of the above
Rate this question:
Transformer
Capacitor
Resistor
Generator
Surge arrestor
Rate this question:
.01 ohms
.5 ohms
5 ohms
10 ohms
25 ohms
Rate this question:
720
2.4
1.2
34,560
Nobody knows!
Rate this question:
Every month
Every 3 months
Every 6 months
Every 12 months
Every 24 months
Rate this question:
Fuse could blow
Ammeter may not work
Voltmeter could be affected
Dangerous voltages could be produced
None of the above
Rate this question:
10 mins to 1 min
60 secs to 30 secs
10 mins to 5 mins
5 mins to 1 min
Rate this question:
The size of the device being tested
The temperature of the device being tested
The ambient temperature
The relative humidity
Rate this question:
Balance the high voltage drop
Improve the power factor of the system
Provide inductive reactive power
Regulate the voltage for variable speed machines
Rate this question:
313 amps
767 amps
939 amps
542 amps
271 amps
Rate this question:
provide power factor correction
Decrease system kVA demand
Provide more efficient utilization of feeders
All of the above
Rate this question:
.05 %
.5 %
1.0%
1.5%
Rate this question:
47
59
86
87
27
Rate this question:
65kV
45kV
55kV
25kV
15kV
Rate this question:
133.3 whr per revolution
8640 whr per revolution
1728 whr per revolution
43200 whr per revolution
Rate this question:
Is measured to detect metals in oil
Is measured in MgKOH/gm
Is measured in dynes/cm
Determines the resistivity of oil
Principally detects impurities in the oil
Rate this question:
Overloaded transformer
Breakers with insufficient interrupting capacity
Protective relays with the wrong settings
Defective equipment grounds
Rate this question:
SF6
Air
Nitrogen
Oxygen
Hydrogen
Rate this question:
269v
115v
460v
622v
135v
Rate this question:
Increase the magnetic field of the blowout coil
Prevent damage to the main contacts
Ensure that a closed circuit is made
Reduce the heating of the trip coil
Reduce the main contact pressure
Rate this question:
3%
4.6%
10%
3.33%
65
Rate this question:
Prevent ground faults
Detect low energy ground faults
Protect personnel from shocks
Provide sensitive short circuit protection
None of the above
Rate this question:
.03 whr per rev
.9 whr per rev
14.4 whr per rev
432 whr per rev
864 whr per rev
Rate this question:
65kV
45kV
55kV
49kV
25kV
Rate this question:
17,184
7,410
12,077
19,246
16,000
Rate this question:
26.4 A
27.2 A
54.4 A
35.3 A
29 A
Rate this question:
39.2 milliwatts
39.2 watts
8.75 watts
56 watts
None of the above
Rate this question:
2,887 kVA
4,328 kVA
6,495 kVA
7,500 kVA
5,000 kVA
Rate this question:
Polarity of the windings
Number of turns in each winding
The turns ration for each tap setting
A,B, and C
A and C only
Rate this question:
5 V
10 V
15 V
20 V
25 V
3 PTs 4-1 ratio, connected delta-delta
3 PTs 4-1 ratio, connected delta-wye
3 PTs 4-1 ratio, connected wye-wye
3 PTs 2.4-1 ratio, connected wye-wye
Rate this question:
8000 A
4000 A
1600 A
2000 A
800 A
Rate this question:
250 VDC
500 VDC
600 VDC
1000 VDC
5000 VDC
Rate this question:
1-2 deg F
1-3 deg C
2-5 deg F
2-5 deg C
3-5 deg C
Rate this question:
28.00
28.75
29.00
20.80
38.75
Rate this question:
Current magnitude times voltage magnitude
Current magnitude times voltage magnitude times % power factor
System energy use
Current magnitude plus voltage magnitude
Rate this question:
230
460
120
480
600
Rate this question:
120 deg
180 deg
0 deg
30 deg
90 deg
Rate this question:
120 deg
180 deg
30 deg
0 deg
90 deg
Rate this question:
120 deg
180 deg
30 deg
0 deg
90 deg
Rate this question:
Quiz Review Timeline (Updated): Jul 28, 2024 +
Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.
Wait!
Here's an interesting quiz for you.