The editorial team at ProProfs Quizzes consists of a select group of subject experts, trivia writers, and quiz masters who have authored over 10,000 quizzes taken by more than 100 million users. This team includes our in-house seasoned quiz moderators and subject matter experts. Our editorial experts, spread across the world, are rigorously trained using our comprehensive guidelines to ensure that you receive the highest quality quizzes.
Learn about Our Editorial Process
| By Ernesto Graciano
E
Ernesto Graciano
Community Contributor
Quizzes Created: 1 | Total Attempts: 100
Questions: 27 | Attempts: 100

SettingsSettingsSettings
Celdas De Media Tensión - Quiz

Bienvenido al Test para Celdas ANSI de Media Tensión


Questions and Answers
  • 1. 

    SafeGear (No Safegear HD) is available in 63 kA fault current ratings

    • A.

      True

    • B.

      False

    Correct Answer
    B. False
    Explanation
    SafeGear (No Safegear HD) is not available in 63 kA fault current ratings.

    Rate this question:

  • 2. 

    1) SafeGear has the smallest footprint available in the industry, which is:

    • A.

      42”w x 95”d

    • B.

      36”w x 85/92”d

    • C.

      36”w x 72”d

    Correct Answer
    B. 36”w x 85/92”d
    Explanation
    The correct answer is 36"w x 85/92"d. This option has the smallest footprint available in the industry compared to the other two options. The dimensions of 42"w x 95"d and 36"w x 72"d are larger and would take up more space. Therefore, the option with the dimensions 36"w x 85/92"d is the correct answer as it has the smallest footprint.

    Rate this question:

  • 3. 

    Which ADVAC generator circuit breakers are available for SafeGear

    • A.

      ADVAC G40

    • B.

      ADVAC G50

    • C.

      Both ADVAC G40 and G50

    Correct Answer
    C. Both ADVAC G40 and G50
    Explanation
    Both the ADVAC G40 and G50 generator circuit breakers are available for SafeGear.

    Rate this question:

  • 4. 

    SafeGear is available with which of the following options?

    • A.

      SwitchgearMD™

    • B.

      SmartRack® remote electric racking device

    • C.

      SafeGear® Digital

    • D.

      All of the above

    Correct Answer
    D. All of the above
    Explanation
    The correct answer is "All of the above" because the question asks for the options available with SafeGear, and all three options mentioned in the question (SwitchgearMD™, SmartRack® remote electric racking device, and SafeGear® Digital) are available with SafeGear.

    Rate this question:

  • 5. 

    Both ADVAC and AMVAC Model 4 circuit breakers are available for use in SafeGear

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    Both the ADVAC and AMVAC Model 4 circuit breakers are available for use in SafeGear. This means that users have the option to choose either of these circuit breakers for their SafeGear system.

    Rate this question:

  • 6. 

    The standard warranty offered with AMVAC breakers is:

    • A.

      1 year

    • B.

      3 years

    • C.

      5 years

    Correct Answer
    C. 5 years
    Explanation
    The standard warranty offered with AMVAC breakers is 5 years. This means that if there are any defects or malfunctions in the breaker within the first 5 years of purchase, the company will cover the cost of repairs or replacement. This longer warranty period indicates that the company has confidence in the durability and quality of their product, giving customers peace of mind and assurance in their investment.

    Rate this question:

  • 7. 

    The breaker that requires the least maintenance in the industry is:

    • A.

      ADVAC

    • B.

      AMVAC

    Correct Answer
    B. AMVAC
    Explanation
    AMVAC is the correct answer because it is a type of breaker that requires the least maintenance in the industry. This implies that compared to other breakers, AMVAC breakers have a longer lifespan and are less prone to malfunctions or breakdowns. This could be due to the advanced technology or design features of AMVAC breakers, which result in a more reliable and durable product. With minimal maintenance requirements, AMVAC breakers offer cost savings and convenience to users, making them a preferred choice in the industry.

    Rate this question:

  • 8. 

    The new ABB line of generator circuit breakers have been tested to which standard?

    • A.

      The new dual logo standard IEC/IEEE – 62271-37-013

    • B.

      IEEE C37.013a

    • C.

      IEC62271-200

    Correct Answer
    A. The new dual logo standard IEC/IEEE – 62271-37-013
    Explanation
    The correct answer is the new dual logo standard IEC/IEEE – 62271-37-013. This means that the ABB line of generator circuit breakers have been tested and meet the requirements of both the IEC (International Electrotechnical Commission) and IEEE (Institute of Electrical and Electronics Engineers) standards as specified in the 62271-37-013 document. This ensures that the circuit breakers are compliant with internationally recognized standards for safety and performance.

    Rate this question:

  • 9. 

    Type 2B construction offers protection to personnel when the LV compartment door is open

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    Type 2B construction offers protection to personnel when the LV compartment door is open. This means that when the door of the low voltage (LV) compartment is open, personnel are still protected from any potential hazards or dangers. This suggests that the construction of Type 2B is designed to ensure the safety of personnel even when the compartment is accessible or open, making the statement true.

    Rate this question:

  • 10. 

    Galvanized steel construction offers what customer benefits?

    • A.

      Superior corrosion resistance

    • B.

      High light reflectivity

    • C.

      Both a and b

    Correct Answer
    C. Both a and b
    Explanation
    Galvanized steel construction offers both superior corrosion resistance and high light reflectivity. The process of galvanizing involves coating the steel with a layer of zinc, which acts as a protective barrier against corrosion. This makes galvanized steel highly resistant to rust and other forms of corrosion, prolonging its lifespan and durability. Additionally, the zinc coating on galvanized steel has high light reflectivity, making it ideal for applications where increased visibility or reflectivity is desired, such as in outdoor signage or highway guardrails. Therefore, both of these benefits are provided by galvanized steel construction.

    Rate this question:

  • 11. 

    The benefit(s) of using the Delrin tipped primary contacts for auxiliary unit primary connections are:

    • A.

      Increased personnel safety and product reliability

    • B.

      Larger PT compartments

    • C.

      Less work for the Engineer

    Correct Answer
    A. Increased personnel safety and product reliability
    Explanation
    Using Delrin tipped primary contacts for auxiliary unit primary connections provides increased personnel safety and product reliability. Delrin is a high-performance plastic that offers excellent electrical insulation properties and is resistant to wear and corrosion. By using Delrin tipped contacts, the risk of electrical shock or injury to personnel is reduced. Additionally, Delrin's durability ensures a reliable electrical connection, minimizing the chances of power interruptions or equipment failures.

    Rate this question:

  • 12. 

    ABB auxiliary compartments are the safest in the industry for operators because:

    • A.

      They utilize closed door racking

    • B.

      The devices can be racked in and out with the SmartRack remote racking system

    • C.

      Both a and b

    Correct Answer
    C. Both a and b
    Explanation
    The correct answer is both a and b. ABB auxiliary compartments are the safest in the industry for operators because they utilize closed door racking, which provides an added layer of protection. Additionally, the devices can be racked in and out with the SmartRack remote racking system, eliminating the need for manual handling and reducing the risk of accidents or injuries.

    Rate this question:

  • 13. 

    The SmartRack electric racking device offers which customer benefits?

    • A.

      Increased personnel safety by allowing the operator to rack the breaker from a safe distance from the switchgear

    • B.

      Being able to rack the auxiliary compartments in and out using the SmartRack

    • C.

      Both a and b

    Correct Answer
    C. Both a and b
    Explanation
    The SmartRack electric racking device offers both increased personnel safety by allowing the operator to rack the breaker from a safe distance from the switchgear, and the ability to rack the auxiliary compartments in and out using the SmartRack.

    Rate this question:

  • 14. 

    Ground and test devices are used for which customer purpose?

    • A.

      Filling empty spaces within the switchgear

    • B.

      Providing a means to safely test and then ground the primary circuits

    • C.

      Open all breakers within the switchgear

    Correct Answer
    B. Providing a means to safely test and then ground the primary circuits
    Explanation
    Ground and test devices are used to safely test and ground the primary circuits. This is important to ensure the safety of the equipment and personnel working with the switchgear. By providing a means to safely test the circuits, any faults or issues can be identified and addressed before they cause any damage or harm. Grounding the circuits helps to prevent electrical hazards and ensures that any excess current is safely directed to the ground. Overall, these devices serve the purpose of maintaining a safe and reliable electrical system.

    Rate this question:

  • 15. 

    The primary benefit(s) of Asset Health monitoring is:

    • A.

      Increase reliability in the system by detecting potential primary insulation break down before it occurs

    • B.

      Improve personnel safety by eliminating the need for IR ports

    • C.

      Both a and b

    Correct Answer
    C. Both a and b
    Explanation
    The primary benefit of Asset Health monitoring is that it increases reliability in the system by detecting potential primary insulation breakdown before it occurs. Additionally, it improves personnel safety by eliminating the need for IR ports. Therefore, the correct answer is both a and b.

    Rate this question:

  • 16. 

    SafeGear with 1200 A main bus and breaker ratings do not require ventilated doors

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    SafeGear with a 1200 A main bus and breaker ratings do not require ventilated doors because they are designed to handle the specified current without overheating. Ventilated doors are typically used to allow for air circulation and cooling in electrical enclosures where high currents are present. However, in the case of SafeGear with a 1200 A main bus and breaker ratings, the design and components used are sufficient to handle the current without the need for additional ventilation.

    Rate this question:

  • 17. 

    Auxiliary compartments can be located over 2000 A breakers but not over 3000 A breakers

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    Auxiliary compartments are additional spaces or compartments located near circuit breakers to house auxiliary equipment such as relays, meters, or control devices. The given statement suggests that these compartments can be located over circuit breakers with a current rating of up to 2000 A, but not over circuit breakers with a current rating of 3000 A or higher. Therefore, the correct answer is true, indicating that auxiliary compartments can be located over 2000 A breakers.

    Rate this question:

  • 18. 

    3000 A and 4000 A breakers can only be located in the bottom breaker compartment

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    The statement is true because the given information states that 3000 A and 4000 A breakers can only be located in the bottom breaker compartment. This implies that these specific types of breakers cannot be placed in any other compartment, such as the top breaker compartment. Therefore, the correct answer is true.

    Rate this question:

  • 19. 

    The ANSI MV Safegear MCC Arc Resistance construction is:

    • A.

      Type 2A

    • B.

      Type 2B

    • C.

      Type 2C

    Correct Answer
    B. Type 2B
    Explanation
    The correct answer for this question is Type 2B. This indicates that the ANSI MV Safegear MCC Arc Resistance construction is of Type 2B.

    Rate this question:

  • 20. 

    The contactor type of the Safegear MCC is:

    • A.

      Fixed

    • B.

      Removable

    • C.

      Withdrawable

    Correct Answer
    C. Withdrawable
    Explanation
    The contactor type of the Safegear MCC is "withdrawable." This means that the contactor can be easily removed or inserted into the MCC without the need for any tools or disconnection of wiring. This feature allows for quick and convenient maintenance or replacement of the contactor, minimizing downtime and ensuring efficient operation of the MCC.

    Rate this question:

  • 21. 

    The Safegear MCC available options includes:

    • A.

      Only Direct On Line (DOL) starter

    • B.

      Reversible and synchronous

    • C.

      Both a) and b)

    Correct Answer
    A. Only Direct On Line (DOL) starter
    Explanation
    The Safegear MCC available options include only the Direct On Line (DOL) starter. This means that the MCC does not offer any other types of starters such as reversible or synchronous starters. Therefore, the correct answer is Only Direct On Line (DOL) starter.

    Rate this question:

  • 22. 

    The Safegear MCC does not require a transition section when coupled to the Safegear Switchgear only if coupling is front aligned

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    The Safegear MCC does not require a transition section when coupled to the Safegear Switchgear only if coupling is front aligned. This means that if the coupling between the two gear systems is aligned at the front, there is no need for a transition section. However, if the coupling is not front aligned, a transition section would be necessary.

    Rate this question:

  • 23. 

    The maximum ratings of the Safegear MCC cell are:

    • A.

      5kV, 2000 A, 50kA

    • B.

      7.2kV, 3000 A, 50kA

    • C.

      12kV, 3000 A, 40kA

    Correct Answer
    B. 7.2kV, 3000 A, 50kA
    Explanation
    The correct answer is 7.2kV, 3000 A, 50kA. This is because it has the highest voltage rating of 7.2kV, the highest current rating of 3000 A, and the same short-circuit current rating of 50kA as the other options. This makes it the most powerful and suitable option for the Safegear MCC cell.

    Rate this question:

  • 24. 

    The available contactor ratings in the Safegear MCC are

    • A.

      400 A

    • B.

      720 A

    • C.

      Both a) and b)

    Correct Answer
    C. Both a) and b)
    Explanation
    The available contactor ratings in the Safegear MCC are both 400 A and 720 A. This means that users have the option to choose between these two ratings depending on their specific needs and requirements. Having multiple options allows for flexibility and ensures that the Safegear MCC can accommodate a wide range of applications and electrical loads.

    Rate this question:

  • 25. 

    The Safegear MCC can be 2H construction (up to 2 contactors per cell) only when 2 contactors are 400 A

    • A.

      True

    • B.

      False

    Correct Answer
    B. False
    Explanation
    The Safegear MCC can be 2H construction (up to 2 contactors per cell) with contactors of any ampere rating, not just 400 A. Therefore, the statement is false.

    Rate this question:

  • 26. 

    In the ANSI solution, the cells can be installed and operate in altitude (more than 1000masl) if surge arresters are installed, but the Insulation level is de-rated including BIL and power frequency

    • A.

      True

    • B.

      False

    Correct Answer
    A. True
    Explanation
    The explanation for the given correct answer is that according to the ANSI solution, cells can be installed and operate in high altitudes (more than 1000masl) if surge arresters are installed. However, in such cases, the insulation level, including BIL (Basic Insulation Level) and power frequency, is de-rated. This means that the insulation level is reduced or downgraded in order to account for the higher altitude, which can affect the performance and reliability of the cells. Therefore, the statement "True" is correct.

    Rate this question:

  • 27. 

    When the Switchgear and MCC frames are direct coupled, the ratings of the complete Line up are the ones of the upper rating of both equipment

    • A.

      True

    • B.

      False

    Correct Answer
    B. False
    Explanation
    When the Switchgear and MCC frames are direct coupled, the ratings of the complete Line up are not necessarily the ones of the upper rating of both equipment. The ratings of the complete lineup depend on various factors such as the individual ratings of the switchgear and MCC frames, their compatibility, and the specific requirements of the system. Therefore, it is not always true that the ratings of the complete lineup will be the ones of the upper rating of both equipment.

    Rate this question:

Quiz Review Timeline +

Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.

  • Current Version
  • Aug 12, 2023
    Quiz Edited by
    ProProfs Editorial Team
  • Jul 15, 2019
    Quiz Created by
    Ernesto Graciano
Back to Top Back to top
Advertisement
×

Wait!
Here's an interesting quiz for you.

We have other quizzes matching your interest.