This quiz, titled '2A672 EDIT CODE 6 40-85,' assesses knowledge on electrical systems in military contexts, specifically focusing on voltage regulators, generator operations, and troubleshooting electrical faults in -86 generator sets.
S46 open
S48 open
S46 closed
S48 closed
Rate this question:
M4 is open
S53 is open
K23 is open
K16 is open
Rate this question:
S1 is in the automatic position
R61 is turned fully clockwise
K16 contacts are closing
K23 contacts are open
Rate this question:
IDLE
GENERATE
BUILD UP VOLTS
AUTO TEST BANK
Rate this question:
S48 open
S46 open
S49 shorted
S22 stuck open
Rate this question:
A2
DS50
S55 is closed
S48 is closed
Rate this question:
Excitation relay K16
Time delay relay K14
Voltage regulator VR1
Automatic manual switch S1
Rate this question:
Voltage rheostat R61
Excitation relay K16
Test bank switch S202
Auto/manual switch S1
Rate this question:
J8, terminal D-F
J8, terminal V-X
VR1, terminal C-R
Automatic-manual switch S1
Rate this question:
Adjust VR1
Adjust R61
Adjust VR1 and R61
Switch S15 to the L-N position
Rate this question:
S2 is open
R46 is is open
K2 is closed
K17 is closed
Rate this question:
K607 de-energizes and K1 De-energizes
K607 energizes and K1 de-energizes
K607 de-energizes and K1 energizes
No effect
Rate this question:
Voltage regulator
Plug interlock relay
Memory time delay relay
Overvoltage/undervoltage relay
Rate this question:
S30 is shorted
S23 is stuck open
K17 contacts are closed
K23 contacts are closed
Rate this question:
Common ground bus
Main circuit breaker
External power source
Last know source of power
Rate this question:
Recognition and verification
Isolation and elimination
Repair and check
Analysis
Rate this question:
Automatic
Manual
Test
Off
Rate this question:
Injector pump
Transfer pump
Injector nozzle
Throttle actuator
Rate this question:
Magnetic Pick up
Engine speed governor
Speed trim potentiometer
Speed control potentiometer
Rate this question:
28.5 VDC
110 VDC
115 VAC
200 VAC
Rate this question:
Only generator output stops
Only the AC contactor opens
AC supply warning light illuminates
AC contactor opens and generator output stops
Rate this question:
Overtemperature
Under frequency
Over frequency
Low fuel
Rate this question:
S1, master switch
S5, run/idle toggle switch
S3 interlock toggle switch
PB2 output control pushbutton switch
Rate this question:
High sence relay (HSR) energizes
Interlock (INT) relay energizes
INT relay de-energizes
HSR De-energizes
Rate this question:
Connect TB4-11 to 14 VDC power source
Check the field transformer
Field flash the generator
Check the fault display
Rate this question:
Second stage impeller
First stage diffuser
Compressor shaft
Torsion shaft
Rate this question:
Air oil seals
Fuel atomizer
Torus assembly
Pneumatic thermostat
Rate this question:
Oil pressure sequencing switch
Oil pressure relief valve
Oil shut off switch
Main oil pump
Rate this question:
Spring tension is less than centrifugal force and the flyweights move outward opening the bypass port
Spring tension is less than centrifugal force and the flyweights move outward closing the bypass port
Spring tension is greater than centrifugal force and the flyweights move inward closing the bypass port
Spring tension is greater than centrifugal force and the flyweights move inward opening the bypass port
Rate this question:
Diaphragm
Rate Control
Load control
Mechanical linkage
Rate this question:
S10 was left on
K17 is energizing
K18 is de-energizing
K16 is de-energizing
Rate this question:
K8
L9
S13
S11
Rate this question:
Check to see if s10 was left on
Nothing this is normal operation
Check to see if the 95 percent centrifugal switch S14 is closed
Check to see if the 95 percent centrifugal switch S14 is open
Rate this question:
The AC voltage drops off line
Its contacts open and energizes K11A
The undervoltage light illuminates
The unit operates normally
Rate this question:
CB1 open
K11B energizes
K11A de-energized
K11 contacts C and D opened
Rate this question:
K6 is defective
TR1 is defective
R6 requires adjustment
S4 is in the off position
Rate this question:
Stater relay
Ignition unit
Ready to load light
Acceleration limiter valve
Rate this question:
Fuel solenoid L1
Fuel level relay K4
Bleed air solenoid
Oil pressure switch S11
Rate this question:
Kilovolts
Kilowatts
Kilo-volt-amperes (KVA)
Kilo-watt-amperes (KWA)
Rate this question:
K110 is energized
K2 is de-energized
CB1 is malfunctioning
CR1 is malfunctioning
Rate this question:
CR1
CR2
S66 AND S67
K3 energized
Rate this question:
CB1
CR1
S56
S1
Alternating Current (AC) load selections switches (S15 though S20) wont work
Ac load selection switches (S15 through S20) work
AC load selection switches (S9 through S14) work
Blower motor B2 wont work
Rate this question:
CB2 is on
CB1 is open
K110 is open
S67 is closed
Rate this question:
12 volts direct current (VDC)
28 VDC
120 volts alternating current (VAC)
208 VAC
Rate this question:
K1
K2
CR2
PT2
Rate this question:
AC voltmeter
Transformer PT3
Blower motor B1
Blower motor B2
Rate this question:
Quiz Review Timeline (Updated): Mar 20, 2023 +
Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.
Wait!
Here's an interesting quiz for you.