2015 Iecc Study Questions

Reviewed by Editorial Team
The ProProfs editorial team is comprised of experienced subject matter experts. They've collectively created over 10,000 quizzes and lessons, serving over 100 million users. Our team includes in-house content moderators and subject matter experts, as well as a global network of rigorously trained contributors. All adhere to our comprehensive editorial guidelines, ensuring the delivery of high-quality content.
Learn about Our Editorial Process
| By Catherine Witting
C
Catherine Witting
Community Contributor
Quizzes Created: 2 | Total Attempts: 2,969
| Attempts: 2,424 | Questions: 119
Please wait...
Question 1 / 119
0 %
0/100
Score 0/100
1. The total estimated annual cost for purchased energy for the building functions regulated by the IECC, including applicable demand charges, is deemed to be the ________. 

Explanation

Sec. 202- Energy cost, definition

Submit
Please wait...
About This Quiz
2015 Iecc Study Questions - Quiz

The 2015 IECC Study Questions quiz assesses knowledge on the International Energy Conservation Code, focusing on building design, energy use, and conservation standards. It is pertinent for professionals in building construction and design, enhancing understanding of energy efficiency requirements.

Tell us your name to personalize your report, certificate & get on the leaderboard!
2. What type of construction work is subject to inspection by the code official?

Explanation

Sec. 104.1

Submit
3. Under which of the following conditions is a residential project exempt from the provisions of the IECC?

Explanation

R501.6

Submit
4. A switch must be sited so that it is readily accessible. Which of the following locations would meet the requirements of the IECC?

Explanation

Sec. 202- Accessible and Readily Accessible- Definition

Submit
5. Where can you find the formula for thermal transmittance?

Explanation

The correct answer is "Sec. 202- U-factor Definition". This is because the U-factor is a measure of thermal transmittance, which is the rate at which heat transfers through a material. Therefore, the formula for thermal transmittance, or U-factor, can be found in Section 202 of a document or resource that defines and explains the U-factor.

Submit
6. Which of the following locations is within the Tropical Climate Zone?

Explanation

Sec. 301.4

Submit
7. Which of the following improvements is not regulated by the IECC?

Explanation

Sec, C503.1, Exception 3

Submit
8. Which of the following components is not regulated by the IECC for walk-in coolers?

Explanation

Secs. C403.2.15, C403.2.16

Submit
9. Which chapters of the IECC apply to residential occupancies?

Explanation

R101.2

Submit
10. Thermostatic setback controls for an HVAC system shall have the capability to set back or temporarily operate the system to maintain zone temperatures down to _____ or up to _____. 

Explanation

Sec. C403.2.4.2.1

Submit
11. Which of the following information should be included on the construction documents to demonstrate compliance with the IECC?

Explanation

Sec. 103.2

Submit
12. Which of the following components is considered automatic?

Explanation

Sec. 202- Automatic, definition

Submit
13. How many different climate zones does Kansas have?

Explanation

Figure 301.1

Submit
14. A 15-foot track light is proposed for a building. Twelve 40-watt fixtures are proposed for the track. Which wattage should be counted toward the interior lighting power of the building?

Explanation

Sec. C405.4.1

Submit
15. The reconstruction and renewal of any part of an existing roof for the purpose of maintenance is the definition of ____________. 

Explanation

Sec. 202- Roof repair, definition

Submit
16. A variable air volume system (VAV) is required 

Explanation

Sec. C403.4.4

Submit
17. Which of the following spaces must be considered when determining the total connected interior lighting power of a hotel?

Explanation

Sec. C405.4.1, Exception 1.2

Submit
18. Which of the following inspections is required by the IECC for a new residential building?

Explanation

Sec. 104.2

Submit
19. Which of the following types of alterations to commercial buildings must comply with the IECC?

Explanation

Sec. C503

Submit
20. Which of the following elements is considered a fenestration product?

Explanation

Sec. 202- Fenestration, definition

Submit
21. According to Chapter 4 [CE], simple HVAC systems and equipment that meet the minimum equipment requirements listed in Tables C403.2.3 (1-9) shall be verified ___________________. 

Explanation

Sec. C403.2.3

Submit
22. A skylight is considered glass or any other transparent or translucent glazing material installed at less than ______ degrees from horizontal. 

Explanation

Sec. C202, Fenestration, Definition

Submit
23. A building addition is considered an extension or increase in the conditioned _____ of a building. 

Explanation

Sec. 202, Addition, Definition

Submit
24. In the preparation of heating and cooling load calculations, what is the maximum interior design temperature for heating?

Explanation

Sec. 302.1

Submit
25. A series of fenestration products used to create an external n-bearing wall that is designed to separate the exterior and interior environments is called a _____. 

Explanation

Sec. 202, Curtain wall, definition

Submit
26. How do the dimensions of a daylight zone under a rooftop monitor differ from the dimensions of a daylight zone next to a window?

Explanation

Sec. C405.2.3.2

Submit
27. The required automatic time clock or programmable controls for an HVAC system shall be able to retain their programming and time setting during a loss of power for a minimum of ______ hours. 

Explanation

Sec. C403.2.4.2.2

Submit
28. What standard is used to determine U-factors?

Explanation

Sec. 303.1.3

Submit
29. A proposed retail sales building will be built in Climate Zone 3. The building will have 20 percent window area to above-grade wall area. What is the minimum R-value requirement for below grade walls?

Explanation

Table C402.1.3

Submit
30. Insulating sheathing must have a core material with a minimum R-value of ________. 

Explanation

Sec. R202-Insulated Sheathing, Definition

Submit
31. The maximum permitted air infiltration rate for storefront glazing is _____ cfm/ft2.

Explanation

Table C402.5.2

Submit
32. What information is required on the construction documents of a commercial building?

Explanation

Sec. 103.2

Submit
33. Which of the following interior building areas are not required to have light reduction controls?

Explanation

Secs. C405.2.1.1, C405.2.2.2

Submit
34. How shall energy code compliance be determined for a three-story building where the first story is in retail space and the second and third stories are multifamily?

Explanation

Sec. 104.4.1

Submit
35. A rigid, opaque weather-resistive covering is applied over insulation on the exterior of a basement wall. The protective covering covers the exposed insulation and extends 12 inches below grade. Are code requirements met?

Explanation

Sec. 303.2.1

Submit
36. Which of the listed commercial buildings must comply with the building thermal envelope provisions of the IECC?

Explanation

Sec. C402.1.1

Submit
37. A retail space is being converted to an office space with no resulting increase in energy demand. No changes are being made to the envelope or mechanical systems. What provisions of the IECC apply?

Explanation

Sec. C505.1

Submit
38. When the requirements of Sections C402 through C405 are not satisfied on an individual basis for those buildings undergoing an addition, alteration, or repair ____________. 

Explanation

C502.1

Submit
39. Using the Building Area Method, what is the maximum interior lighting power allowance for a 10,000 square-foot fast-food restaurant in a single occupancy building?

Explanation

The maximum interior lighting power allowance for a 10,000 square-foot fast-food restaurant in a single occupancy building is 9,000 watts. The Building Area Method is a calculation method used to determine the lighting power allowance based on the area of the building. In this case, the lighting power allowance is determined to be 0.9 watts per square foot, resulting in a maximum allowance of 9,000 watts for a 10,000 square-foot restaurant.

Submit
40. Which of the following assemblies is not considered part of the building thermal envelope?

Explanation

Sec. 202- Building Thermal Envelope and Conditioned Space- Definition

Submit
41. Which of the following lighting system requirements is applicable to warehouses?

Explanation

Sec. C405.2.1.2

Submit
42. Sealing of openings and penetrations to prevent air leakage in a commercial building envelope ______. 

Explanation

Sec. C402.5.2

Submit
43. Duct systems designed to operate at static pressures in excess of 3 inches w.g. must be leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual with a maximum air leakage rate of _________. 

Explanation

Sec. C403.2.9.1.3

Submit
44. In a hydronic system, a two-position valve is required on each hydronic heat pump unless the total pump system power is a maximum of ______ horsepower. 

Explanation

Sec. C403.4.2.3.3

Submit
45. Design loads for simple HVAC heating and cooling systems are to be determined _________________. 

Explanation

Sec. C403.2.1

Submit
46. An unconditioned warehouse will be constructed. The warehouse will have a ceiling height of 30 feet. Using the Building Area Method, what is the maximum interior lighting power allowance for the warehouse if the total area is 50,000 square feet?

Explanation

The Building Area Method is a method used to determine the maximum interior lighting power allowance for a building based on its total area. According to this method, the maximum interior lighting power allowance is calculated by multiplying the total area of the building by a predetermined lighting power density value. In this case, since the total area of the warehouse is given as 50,000 square feet, and the lighting power density value for an unconditioned warehouse with a ceiling height of 30 feet is 0.66 watts per square foot, the maximum interior lighting power allowance would be 33,000 watts (50,000 square feet * 0.66 watts per square foot).

Submit
47. When used to control both heating and cooling, zone thermostatic controls shall provide a dead band of at least ________. 

Explanation

Sec. C403.2.4.1.2

Submit
48. What is the dimension of the daylight zone in a large, open space next to a 4-foot by 4-foot window that has a 6-foot head height?

Explanation

not-available-via-ai

Submit
49. When calculating interior lighting power using the Building Area Method, what is the total allowable wattage of a 20,000 square foot office building?

Explanation

Table C405.4.2(1)

Submit
50. Based on the occupancy classification and number of stories, which one of the following occupancies is considered a commercial building under the IECC?

Explanation

Sec. 202, Residential Building, Definition

Submit
51. Cargo doors and loading dock doors shall be equipped with _______ to restrict infiltration when vehicles are parked in the doorway. 

Explanation

Sec. C402.5.6

Submit
52. The maximum length of a 3/8- inch water supply pipe between the source of heated water and the termination of the fixture supply pipe for a lavatory faucet is ___________. 

Explanation

The maximum length of a 3/8-inch water supply pipe between the source of heated water and the termination of the fixture supply pipe for a lavatory faucet is 3 feet. This means that the distance between the source of heated water and the lavatory faucet should not exceed 3 feet for a 3/8-inch water supply pipe.

Submit
53. An HVAC fan system that is designed to serve multiple building zones and that utilizes multiple thermostats is referred to in the code as a __________.

Explanation

Sec. C403.4.4

Submit
54. Operating and maintenance manuals, along with all required reports and drawings, shall be provided to the building owner a maximum of _______ days after the date of receipt of the certificate of occupancy. 

Explanation

Secs. C403.2.11, C408.2.5

Submit
55. A wall-mounted canopy kitchen hood has an airflow rate of 4,000 cfm and will be installed over medium-duty equipment. Which of the following statements is/are correct?

Explanation

Sec. C403.2.8

Submit
56. Economizers are not required on individual direct expansion cooling coil units having a supply capacity less than ______ Btu/h. 

Explanation

Sec. C403.3, Exception #2.1

Submit
57. A gravity damper is proposed for an exhaust duct with a 250 cfm airflow in a four-story building located in Climate Zone 4. Does this comply with the IECC?

Explanation

Sec. C403.2.4.3

Submit
58. The automatic controls required for a snow-melting system shall be capable of shutting off the system when the pavement temperature is above _____ and no precipitation is falling. 

Explanation

Sec. C403.2.4.5

Submit
59. Economizers are never required in which of the following climate zones?

Explanation

Sec. C403.3, Exception #1

Submit
60. What is the specified intent of the IECC?

Explanation

Sec. 101.3

Submit
61. What is the area of the toplight daylight zone under a 4-foot by 8-foot skylight in a warehouse with 20-foot ceilings? The highest obstruction in the warehouse is 10 feet high, and there are no buildings or geological formations that block sunlight. 

Explanation

Sec, C405.2.3.3

Submit
62. A proposed alteration will include replacing 75 percent of the existing luminaries in an office space. The alteration will not increase the installed interior lighting power. Will this alteration need to comply with the IECC?

Explanation

Sec. C503.1, Exception 7

Submit
63. A 10,000 square foot building located in Climate Zone 7 will have a primary entrance door opening directly from a 2,500 square foot space to the exterior. A swinging door with a self-closing device will be installed. Does the door comply with the IECC vestibule requirements?

Explanation

Sec. C402.5.7, Exception 4

Submit
64. A 10,000-square-foot commercial building will include no space conditioning equipment. The building will include a lighting system. Which portions of the energy using features must comply with the IECC?

Explanation

Sec. C402.1.1

Submit
65. Which of the following is true concerning a conflict between a reference standard and a provision of the IECC?

Explanation

Sec. 106.1.1

Submit
66. A 25,000 square foot warehouse is currently conditioned for freeze protection only and uses less than 3.4 Btu/h per square foot. It is being converted to a fully conditioned space. Which portions of the IECC apply?

Explanation

Sec. C503.2

Submit
67. Which of the listed occupancies are considered residential buildings by the IECC if no more than three stories above grade plane?

Explanation

R101.2, 202

Submit
68. When must an alteration on an historic building comply with the provisions of the IECC?

Explanation

Sec. 501.6

Submit
69. A sunroom is considered a one-story structure attached to a dwelling with a glazing area in excess of ____ percent of the gross area of the structure's exterior walls and roof. 

Explanation

Sec. R202- Sunroom, Definition

Submit
70. Which of the following statements regarding a change in commercial occupancy is accurate?

Explanation

Sec. C505.1

Submit
71. When applying the prescriptive building envelope provisions for commercial buildings, what is the maximum permitted U-factor of a side-hinged swinging opaque door for a building located in Climate Zone 3?

Explanation

Table C402.1.4

Submit
72. Which of the following HVAC systems must be divided into separate isolation areas?

Explanation

Sec. C403.2.4.4

Submit
73. In general, all supply and return air ducts located in unconditioned spaces must be insulated to a minimum of _____ insulation. 

Explanation

Sec. C403.2.9

Submit
74. A metal warehouse building is proposed in Climate Zone 2. The building will use a metal purlin system with an R-5 thermal block. R-30 insulation is proposed to be installed between the roof framing members. Does this installation comply with the prescriptive building envelope requirements of the IECC?

Explanation

Table C402.1.3

Submit
75. Which of the following methods and materials are approved for duct sealant for low-pressure duct systems?

Explanation

C403.2.9.1.1

Submit
76. What is the maximum average power usage of an ice-cream temperature, self-contained, vertical solid door freezer with a case volume of 80 square feet, as measured in accordance with AHRI 1200, Appendix C?

Explanation

Table C403.2.14(2)

Submit
77. According to the prescriptive insulation requirements of Chapter 4 [CE], an above-grade wood-framed wall in a commercial office building in Climate Zone 7, with a window area of 10 percent of the above-ground wall area, shall have a minimum required R-value of ___________. 

Explanation

Table C402.1.4

Submit
78. An interior space designated as a security or emergency area that must be continuously lighted during normal building operating hours _________. 

Explanation

Sec. C405.2, Exception 1

Submit
79. Gas-fired boilers are proposed for heating water in a new building. Which of the following combinations is compliant?

Explanation

Secs. C404.2.1, C403.4.2.5 and Table C403.2.3(5)

Submit
80. A cold-formed steel stud wall with 6-inch studs spaces at 16 inches on center is filled with R-19 batt insulation and covered with R-7.5 rigid, continuous insulation. The other building materials have a cumulative R-value of 1.5. What U-factor should be used when determining compliance with Table C402.1.4?

Explanation

Sec. C402.1.4.1

Submit
81. When documenting the total connected lighting power for a proposed building, what wattage should be used for a screw lamp holder?

Explanation

Sec. C405.4.1

Submit
82. Outdoor piping contains a water and ethylene glycol mixture, which is safely protected from freezing at conditions above 15 F. What must be true of the freeze protection controls if the piping is heat traced?

Explanation

Sec. C403.2.4

Submit
83. A built-up mechanical system using a chiller and boiler will serve the space conditioning needs of a commercial building. The designer has proposed a water economizer that can provide at least 80 percent of the expected system cooling capacity at 50F dry bulb and 45F wet bulb and below. Will this economizer meet the minimum requirements?

Explanation

Sec. C403.4.1

Submit
84. A heated-water circulation system is proposed for a new family restaurant. Which factors determine the maximum allowable pipe length permissible in the circulation loop?

Explanation

Sec. C404.6

Submit
85. Gravity dampers for both outdoor air supply and exhaust ducts shall be permitted in all of the following except ______. 

Explanation

Sec. C403.2.4.3

Submit
86. Heat traps are required on ___________. 

Explanation

Sec. C404.3

Submit
87. A warehouse building located in Helena, Montana will utilize a heated slab-on-grade floor. R-10 insulation will be installed starting from the bottom of the slab down for a distance of 18 inches. Does this installation comply with Section C402?

Explanation

Tables C301.1 and C402.1.3

Submit
88. Which of the listed occupancies are considered commercial occupancies under the IECC?

Explanation

C101.2, 202

Submit
89. Within industrial facilities, the maximum floor area permitted to be controlled by a single override switch for an automatic time switch control device shall be _____ square feet.

Explanation

Sec. C405.2.2.1, Exception 1.2

Submit
90. A cooling duct is located in an unconditioned space. The design temperature of the air inside the duct system is 55F, and the design temperature of the space where the duct is located is 68F. What minimum duct insulation R-value is required for this duct?

Explanation

Sec. C403.2.9, Exception 2

Submit
91. A damper is located in a wall system that surrounds an elevator shaft in a seven-story building. What is the maximum air leakage rate to meet the damper requirement?

Explanation

Secs. C402.5.5, C403.2.4.3

Submit
92. Calhoun County, Illinois, is located in which climate zone?

Explanation

Table 301.1

Submit
93. A proposed manufacturing building located in Climate Zone Marine 4 will use a CMU wall system for 60 percent of the building with the remaining 40 percent of the building constructed using metal framing. What is the minimum required R-value for insulation for the metal wall system given the percent of CMU that is proposed for the building?

Explanation

Table C402.1.3

Submit
94. A Group R-1 hotel is proposed for a Climate Zone 3 location. The building will utilize mass walls for the exterior wall system. What is the minimum required R-value requirement for the wall system using the prescriptive thermal envelope requirements of the IECC?

Explanation

Table C402.1.3

Submit
95. When evaluating equipment compliance for a complex HVAC system, what is the minimum efficiency of a warm-air gas-fired unit heater at maximum capacity?

Explanation

Table C403.2.3(4)

Submit
96. A 450-square-foot building that will house electronic equipment is to be built in Butte County, Idaho. In order to be exempt from the building thermal envelope provisions of the code, what must be true regarding the average wall and roof U-factor?

Explanation

Sec. C402.1.2 and Table C301.1

Submit
97. An alteration to an existing 50,000 square foot commercial building will include a new cooling system with an output capacity of 165,000 Btu/h. This alteration will also include a new lighting system. Which energy-saving features must comply with the IECC?

Explanation

Sec. C503.1

Submit
98. IECC Chapter 4 [CE] establishes design criteria applicable to _____________.

Explanation

Sec. C401.1

Submit
99. Gravity (nonmotorized) leakage-rated dampers may be used at outdoor air intakes and exhaust openings in lieu of motorized dampers in buildings a maximum of _______ stories in height above grade in Climate Zones 4-8. 

Explanation

Sec. C403.2.4.3, Exception 1

Submit
100. Using the prescriptive thermal envelope requirements of Chapter 4 [CE], which of the following insulation installations will meet the requirements for a metal roof system on a warehouse located in Climate Zone 1?

Explanation

Table C402.1.3

Submit
101. Which of the following statements is not true?

Explanation

Sec. C405.2.4

Submit
102. A conditioned warehouse building located in Climate Zone 7 will incorporate 4,000 square feet of opaque roll-up door. The above grade wall area is 10,000 square feet, and will contain 1,000 square feet of vertical fenestration in addition to the roll up doors. Can the building use Section C402, Building Envelope Requirements, to comply with the International Energy Conservation Code?

Explanation

Sec. C402.1.3

Submit
103. A building's total connected interior lighting power shall include the sum of the watts of all interior lighting equipment __________.

Explanation

Sec. C405.4.1, Exception 1.2

Submit
104. According to the prescriptive building envelope provisions for Chapter 4 [CE], what is the minimum required R-value of an exterior wall of a metal building with a window and glazed door area of 45 percent for an office building located in Climate Zone 2?

Explanation

Secs. C402.1, C402.1.5

Submit
105. Additional lighting is needed for a specific area of a retail store where cosmetics are sampled and sold. What is the additional interior lighting power allowance permitted for the cosmetics area?

Explanation

Sec. C405.4.2.2.1

Submit
106. What wattage should be documented for an 8-foot track light with three 60-watt bulbs proposed for the track?

Explanation

Sec. C405.4.1

Submit
107. When calculating interior lighting power using the Space-by-Space method, what is the total allowable wattage of general lighting for a building containing an 80,000 square foot grocery and a 5,000 square foot family dining restaurant?

Explanation

Table C405.4.2(2)

Submit
108. A 28,000 square foot enclosed parking garage with no heating or mechanical cooling system supplies fresh air through a ventilation system with a total nameplate power of 28 hp. Are modulation airflow rates as specified in Section C403.2.6.2 required?

Explanation

Sec. C403.2.6.2

Submit
109. What is the standard for measuring the efficiency and pressure loss of drain-water heat-recovery units?

Explanation

Sec. C404.8

Submit
110. When using the prescriptive insulation requirements for the building envelope, what is the minimum required R-value of a metal-framed above-grade wall of a commercial building located in Climate Zone 6?

Explanation

Table C402.1.3

Submit
111. Which of the following building envelope features may be traded-off using an IECC Section C407, Total Building Performance, approach?

Explanation

Sec. C401.2, #3

Submit
112. A commercial building located in Clay County, Minnesota, will have a gross above grade wall area of 15,000 ft. The proposed building will have a vertical fenestration area of 5,750 ft2. Are the prescriptive fenestration provisions of Section C402.4 applicable to this building?

Explanation

Table C301.1 and Sec. C402.4.1.1

Submit
113. A proposed international location has the following climate conditions:
  • mean temperature of the coldest month: 33F
  • warmest month mean: 65 F
  • number of months with a mean temperature over 50F: 5
  • dry season: summer
  • heaviest precipitation months: October through March (3x as much precipitation as month with least amount of precipitation)
  • heating degree days: 4,500 (IP units)
To which climate zone does this location belong to?

Explanation

Tables 301.3(1) and (2)

Submit
114. A lobby of a hotel located in Climate Zone 2 will use a revolving door for the primary entrance into the space. The lobby is 5,000 square feet. An adjacent swinging door required by the IBC also serves the lobby. Which of the doors is required to have a vestibule?

Explanation

Sec. C402.5.7, Exceptions 1 and 5

Submit
115. Which of the following is NOT a key change introduced in the 2015 International Energy Conservation Code (IECC)?

Explanation

The 2015 IECC focused on improving energy efficiency in buildings through stricter requirements for building envelopes, lighting, and HVAC systems. It did not mandate renewable energy systems in all new buildings, but it encouraged their adoption through incentives and credits.

Submit
116. In the prescriptive evaluation of the opaque thermal envelope requirements, what is the required minimum R-value for a framed floor system over unconditioned space in a commercial building located in Climate Zone 5?

Explanation

Table C402.1.3

Submit
117. A packaged heating and cooling system will be installed on a retail space in a strip shopping center. Heating and cooling loads were calculated to size the system. The cooling load was calculated at 75,000 Btu/h. The heating load was calculated at 45,000 Btu/h. Which system meets the equipment and system sizing requirements of the IECC based on the output capacities given?

Explanation

Sec. C403.2.2

Submit
118. The minimum required efficiency of a gas-fired steam boiler having an input rating less than 300,000 BTU is ________. 

Explanation

Table C403.2.3(5)

Submit
119. What is the value of D in Equation 4-2 for a building in Climate Zone 7 with the following specifications?
  • 4,000 square feet of exterior wall area
  • 2,000 square feet of windows
  • Window assembly U-factors of 0.30
  • Opaque wall assembly U-factor of 0.045

Explanation

Sec. C402.1.5

Submit
View My Results

Quiz Review Timeline (Updated): Jan 29, 2025 +

Our quizzes are rigorously reviewed, monitored and continuously updated by our expert board to maintain accuracy, relevance, and timeliness.

  • Current Version
  • Jan 29, 2025
    Quiz Edited by
    ProProfs Editorial Team
  • Feb 17, 2020
    Quiz Created by
    Catherine Witting
Cancel
  • All
    All (119)
  • Unanswered
    Unanswered ()
  • Answered
    Answered ()
The total estimated annual cost for purchased energy for the building...
What type of construction work is subject to inspection by the code...
Under which of the following conditions is a residential project...
A switch must be sited so that it is readily accessible. Which of the...
Where can you find the formula for thermal transmittance?
Which of the following locations is within the Tropical Climate Zone?
Which of the following improvements is not regulated by the IECC?
Which of the following components is not regulated by the IECC for...
Which chapters of the IECC apply to residential occupancies?
Thermostatic setback controls for an HVAC system shall have the...
Which of the following information should be included on the...
Which of the following components is considered automatic?
How many different climate zones does Kansas have?
A 15-foot track light is proposed for a building. Twelve 40-watt...
The reconstruction and renewal of any part of an existing roof for the...
A variable air volume system (VAV) is required 
Which of the following spaces must be considered when determining the...
Which of the following inspections is required by the IECC for a new...
Which of the following types of alterations to commercial buildings...
Which of the following elements is considered a fenestration product?
According to Chapter 4 [CE], simple HVAC systems and equipment that...
A skylight is considered glass or any other transparent or translucent...
A building addition is considered an extension or increase in the...
In the preparation of heating and cooling load calculations, what is...
A series of fenestration products used to create an external n-bearing...
How do the dimensions of a daylight zone under a rooftop monitor...
The required automatic time clock or programmable controls for an HVAC...
What standard is used to determine U-factors?
A proposed retail sales building will be built in Climate Zone 3. The...
Insulating sheathing must have a core material with a minimum R-value...
The maximum permitted air infiltration rate for storefront glazing is...
What information is required on the construction documents of a...
Which of the following interior building areas are not required to...
How shall energy code compliance be determined for a three-story...
A rigid, opaque weather-resistive covering is applied over insulation...
Which of the listed commercial buildings must comply with the building...
A retail space is being converted to an office space with no resulting...
When the requirements of Sections C402 through C405 are not satisfied...
Using the Building Area Method, what is the maximum interior lighting...
Which of the following assemblies is not considered part of the...
Which of the following lighting system requirements is applicable to...
Sealing of openings and penetrations to prevent air leakage in a...
Duct systems designed to operate at static pressures in excess of 3...
In a hydronic system, a two-position valve is required on each...
Design loads for simple HVAC heating and cooling systems are to be...
An unconditioned warehouse will be constructed. The warehouse will...
When used to control both heating and cooling, zone thermostatic...
What is the dimension of the daylight zone in a large, open space next...
When calculating interior lighting power using the Building Area...
Based on the occupancy classification and number of stories, which one...
Cargo doors and loading dock doors shall be equipped with _______ to...
The maximum length of a 3/8- inch water supply pipe between the source...
An HVAC fan system that is designed to serve multiple building zones...
Operating and maintenance manuals, along with all required reports and...
A wall-mounted canopy kitchen hood has an airflow rate of 4,000 cfm...
Economizers are not required on individual direct expansion cooling...
A gravity damper is proposed for an exhaust duct with a 250 cfm...
The automatic controls required for a snow-melting system shall be...
Economizers are never required in which of the following climate...
What is the specified intent of the IECC?
What is the area of the toplight daylight zone under a 4-foot by...
A proposed alteration will include replacing 75 percent of the...
A 10,000 square foot building located in Climate Zone 7 will have a...
A 10,000-square-foot commercial building will include no space...
Which of the following is true concerning a conflict between a...
A 25,000 square foot warehouse is currently conditioned for freeze...
Which of the listed occupancies are considered residential buildings...
When must an alteration on an historic building comply with the...
A sunroom is considered a one-story structure attached to a dwelling...
Which of the following statements regarding a change in commercial...
When applying the prescriptive building envelope provisions for...
Which of the following HVAC systems must be divided into separate...
In general, all supply and return air ducts located in unconditioned...
A metal warehouse building is proposed in Climate Zone 2. The building...
Which of the following methods and materials are approved for duct...
What is the maximum average power usage of an ice-cream temperature,...
According to the prescriptive insulation requirements of Chapter 4...
An interior space designated as a security or emergency area that must...
Gas-fired boilers are proposed for heating water in a new building....
A cold-formed steel stud wall with 6-inch studs spaces at 16 inches on...
When documenting the total connected lighting power for a proposed...
Outdoor piping contains a water and ethylene glycol mixture, which is...
A built-up mechanical system using a chiller and boiler will serve the...
A heated-water circulation system is proposed for a new family...
Gravity dampers for both outdoor air supply and exhaust ducts shall be...
Heat traps are required on ___________. 
A warehouse building located in Helena, Montana will utilize a heated...
Which of the listed occupancies are considered commercial occupancies...
Within industrial facilities, the maximum floor area permitted to be...
A cooling duct is located in an unconditioned space. The design...
A damper is located in a wall system that surrounds an elevator shaft...
Calhoun County, Illinois, is located in which climate zone?
A proposed manufacturing building located in Climate Zone Marine 4...
A Group R-1 hotel is proposed for a Climate Zone 3 location. The...
When evaluating equipment compliance for a complex HVAC system, what...
A 450-square-foot building that will house electronic equipment is to...
An alteration to an existing 50,000 square foot commercial building...
IECC Chapter 4 [CE] establishes design criteria applicable to...
Gravity (nonmotorized) leakage-rated dampers may be used at outdoor...
Using the prescriptive thermal envelope requirements of Chapter 4...
Which of the following statements is not true?
A conditioned warehouse building located in Climate Zone 7 will...
A building's total connected interior lighting power shall include...
According to the prescriptive building envelope provisions for Chapter...
Additional lighting is needed for a specific area of a retail store...
What wattage should be documented for an 8-foot track light with three...
When calculating interior lighting power using the Space-by-Space...
A 28,000 square foot enclosed parking garage with no heating or...
What is the standard for measuring the efficiency and pressure loss of...
When using the prescriptive insulation requirements for the building...
Which of the following building envelope features may be traded-off...
A commercial building located in Clay County, Minnesota, will have a...
A proposed international location has the following climate...
A lobby of a hotel located in Climate Zone 2 will use a revolving door...
Which of the following is NOT a key change introduced in the 2015...
In the prescriptive evaluation of the opaque thermal envelope...
A packaged heating and cooling system will be installed on a retail...
The minimum required efficiency of a gas-fired steam boiler having an...
What is the value of D in Equation 4-2 for a building in Climate Zone...
Alert!

Advertisement